39
(A) PV string
(B) Inverter
(C) Tracking control box
(D) Grid
(E) Monitoring device
(F) AC circuit breaker
table 5-1 Cable Requirements
No.
Cable
Type
Specification
Cable Diame-
ter(mm)
Cross-sectional Area(mm
2
)
1
DC cable
PV cable com-
plying with
1,500V standard
4.7 ~ 6.4
4 ~ 6
2
Tracking
system
power
cable
Outdoor double-
core copper wire
cable
8 ~ 18
0.5 ~ 10 (Recommended 4 ~
6)
3
External
ground-
ing cable
Outdoor single-
core copper wire
cable
/
The same as that of the PE
wire in the AC cable
4
Commu-
nication
cable
Shielded twisted
pair
4 ~ 11
0.2 ~ 1.3
The AC cable sealing plate delivered with the inverter varies. The actual product received
shall prevail.
The sealing plate and the required AC cables are as follows.