Electrical Connection
Death hazards due to high voltage existing inside the inverter!
Make sure that all the DC and AC cables to the inverter are not live before
you start the electrical work.
Do not turn on the AC side or DC side circuit breaker until all inverter
electrical connections have completed.
Do not open the enclosure when the inverter is under voltage.
There is a risk of inverter damage or personal injury!
4.1
Cable Requirements
Cable
Conductor size
Recommended
conductor size
AC Cable
8AWG...5AWG 8...16mm²
---
DC Cables
12AWG...10AWG 4...6mm²
11AWG 4mm²
RS485 Comm. Cables
Twist-pair type cable or Twist-pair
type shielding Ethernet cable
-
Second PE Cable
10AWG
…
8AWG 6mm²
9AWG 6mm²