In the European region, such as Sweden, Norway, Hungary, Portugal, Romania,
Greece, Ukraine etc. whose grid code complies with EN50549, select the parame-
ter EN50549_1 (LV grid- connection) or EN50549_2 (MV grid-connection) with
proper manual settings.
In the Brazilian region, set the country code as "Brazil". Selecting "Brazil_230" or
"Brazil_240" will cause setting failure.
For SG30CX, set the grid code as EN50549 in the Ukraine region and apply man-
ual settings for country code compliance.
step 5 When the country is set to Australia, additionally set the applicable network service provider
and then the grid type.Tap
Power Company
to select the correct power company.
figure 7-5
Initialization Power Company
The image shown here is for reference only. Refer to the actual interface for the supported
network service providers.
table 7-1 Power Company Information
Network Service Provider
Grid Type
AS/NZS 4777.2:2015
/
AS/NZS 4777.2:2020 Australia A
/
AS/NZS 4777.2:2020 Australia B
/
AS/NZS 4777.2:2020 Australia C
/
ENERGEX & Ergon Energy
•
STNW1170: single phase < 10 kVA &
three phase < 30 kVA
•
STNW1174 :30 kVA
<
PN ≤ 1500 kVA
Endeavour Energy
MDI 0043
Ausgrid
NS194
Jemena
•
≤ 10kVA per phase (or 30 kVA per three
phase)
•
ELE GU 0014: 30-200kVA