94
Parameters
SG30CX
(1)
SG30CX
(2)
SG33CX
Power factor at nominal
power / Adjustable power
factor
> 0.99 / 0.8 leading – 0.8 lagging
Feed-in phases / AC
connection
3/3
Efficiency
Max. efficiency / European
efficiency
98.6% / 98.3%
Protection
DC
reverse polarity protection
Yes
AC short circuit protection
Yes
Leakage current protection
Yes
Grid monitoring
Yes
Ground fault monitoring
Yes
DC switch
Yes
AC switch
No
PV string monitoring
Yes
Q at night function
Yes
PID recovery function
Yes
DC Terminal Protective
Cover
Yes
/
/
Arc fault circuit interrupter
(AFCI)
/
/
Opt.
Surge protection
DC Type II / AC
Type II
DC Type II / AC
Type II
DC Type II (Type I
+ II Opt.) / AC Type
II
General Data
Dimensions (W*H*D)
702×595×310mm
Weight
50kg
Topology
Transformerless
Degree of protection
IP66
Night power consumption
≤2 W
Operating ambient tempera-
ture range
-30 to 60
℃
(> 45
℃
derating)
Allowable relative humidity
range
0 - 100%
Cooling method
Smart forced air cooling
User Manual