4 Installation Guide
User Manual
20
No.
Description
A
Cable (e.g. “PV1+”, “PV2+”… “PV1-”, “PV2-” etc.)
B
Conduit
Select the terminal according to the cable specification. For example, LT160012
where 16 means that the cable specification is 16mm
2
; 12 means that the
length of the crimping tube is 12mm.
12mm
16mm
2
Cable
Tab. 4-1
Stripping length
Cross-section
Terminal type
Stripped length (mm)
Force (N)
2.5mm
2
LT025008
10±0.5
200
4mm
2
LT040010
12±0.5
270
6mm
2
LT060012
15±0.5
450
10mm
2
LT100012
15±0.5
500
16mm
2
LT160012
16±0.5
1500
Step 3
Crimp the cable. Insert the stripped cable into the terminal. Crimp the
cable using special tool (mouth of the crimping plier should match the
cable cross section), see the following figure.
Step 4
As shown in the following figure, connect the terminal to the
corresponding terminal of the PVS.