System Manual
35
Step 2
Strip off the insulation cover of the cable with a stripped length of 5mm longer than the
depth of the cable lug.
L=D+5mm
D
Cable
lug
Step 3
Crimp the cable lug.
1. Insert the stripped cable into the cable lug.
2. Tighten the cable lug with relevant tools. The crimping number should be more than
two.
Step 4
Insert the heat-shrinkable tubing.
1. A tubing with length of 2cm longer than the depth of the cable lug is recommended.
2. Insert the heat-shrinkable tubing into the cable lug.
3. Shrink the tubing with a hot air blower.
Cable protectors are recommended in the cable crosses if the multi-core
cables are used.
Step 5
Connect the cable.
1. Fasten the cable connection terminals according to the order shown in the figure below.
Summary of Contents for MVS6250
Page 2: ......