SUNFAR E300 SERIES 35
During motor dec process, carry out volt losing speed protect valve. When inverter inner DC
side pump increasing due to dec is higher than this parameter stated value, it will prolong dec
time automatically shown as fig 6-15.
[ F 3 . 1 2 ]
F r e q
T
T
D e c t i m e a d j u s t m e n t
D C v o l t
Fig 6-15 Volt losing speed protection during dec
F3.13 Current limit amplitude level Setting range: 150 ~ 250 (
%
)
It is used for inverter allowable output max current showing as inverter rated current percentage.
Whatever running state (acc, dec or stable running), when inverter output current is higher than
this parameter setting value, inverter will adjust output freq to limit current in rated range,
avoiding over-current tripping.
F3.14 Program version Setting range: 1800 ~ 1899
Inverter control software version. Read only.
6.5 Communication function parameter unit
Set characteristics related to communication.
F4.0 Communication set Setting range
:
0000 ~ 0125
1
st
of LED
:
Baud rate selection
0
:
Reserved 1
:
1200bps 2
:
2400bps
3
:
4800bps 4
:
9600bps 5
:
19200bps
When use serial communication, make sure communication two sides have
the same baud rate.
2
nd
of LED
:
Data format selection
0
:
No check 1
:
Even check 2
:
Odd check
When use serial communication, make sure communication two sides have the same data
format.
E300 Series Mini-type Integrated Universal Inverter Manual