F i b e r O p t i c S o l u t i o n s P r o v i d e r
5/8
www.suntelecom.cn • +86-21-60138638 • [email protected]
3.3.3
Fix the armored fiber cable to the cable fixed board with hose clamp and
fix the strength member to the grounding copper column.
3.3.4
Connect the ground wire is to the cable fixing plate, and then connect it
with room ground.
3.4
The cabinet adopts combinations step rubber bushing for different
diameter cable into the box. The open aperture of the rubber bushings
should be at least 2mm smaller than the diameter of the fiber cable.
3.5
Thread the stripped fiber into the serpentine hose, and fix the serpentine
hose on the binding wire board and then introduce into the splice tray
according to the natural curvature.
3.6
Thread the optical fiber splice protection sleeves into the fiber core, and
then splice the ends of the fiber core with the ends of the pigtail core
and then drive them into the splice tray. (Each splice tray can splice 12
single -core optical fiber.)
3.7
Introduce the spliced pigtail to the patch panel and insert it to
corresponding adapter.
3.8
Fiber-optic lines are connected and scheduled through cross-connection
with the pigtails. The best length of the pigtail is from 1meter to 1.5
meter.
3.9
When does not require scheduling, the trunk cable and drop cable can be
placed directly into the splice tray for protection after being spliced.