SPARC T4-1 Server Installation Guide • August 2013
Caution –
Equipment Loading:
Always load equipment into a rack from the bottom
up so that the rack will not become top-heavy and tip over. Deploy your rack’s
anti-tip bar to prevent the rack from tipping during equipment installation.
Caution –
Elevated Operating Ambient Temperature
: If the server is installed in a
closed or multi-unit rack assembly, the operating ambient temperature of the rack
environment might be greater than room ambient temperature. Therefore, install the
equipment only in an environment compatible with the maximum ambient
temperature (Tma) specified for the server.
Caution –
Reduced Air Flow
: Install the equipment in a rack so that the amount of
air flow is adequate for the safe operation of the equipment.
Caution –
Mechanical Loading
: Mount the equipment in the rack so that the weight
is distributed evenly. A hazardous condition can exist with uneven mechanical
loading.
Rack horizontal opening and unit
vertical pitch
Conforms to ANSI/EIA 310-D-1992 or IEC 60927
standards.
Rack rail mounting hole sizes
Only 9.5 mm square hole and M6 round mounting
holes are supported. All other sizes, including
7.2 mm, M5, or 10-32 mounting holes, are
not
supported.
Distance between front and rear
mounting planes
Minimum 622 mm and maximum 895 mm
(24.5 inches to 35.25 inches).
Clearance depth in front of front
mounting plane
Distance to front cabinet door is at least 27 mm
(1.06 inch).
Clearance depth behind front
mounting plane
Distance to rear cabinet door is at least 900 mm (35.5
inches) with the cable management arm, or 770 mm
(30.4 inches) without the cable management arm.
Clearance width between front and
rear mounting planes
Distance between structural supports and cable
troughs is at least 456 mm (18 inches).
Item
Requirement