2-22
Sun Netra CP3220 Blade Server User’s Guide • January 2010
FIGURE 2-5
Installing a DIMM
6. Press the top edge of the DIMM toward the blade server until the retainer clips
click into place in the notches on the DIMM sides (
FIGURE 2-5
).
The small metal retainer clips on each side of the DIMM slot are spring-loaded,
and they should click into place in the notches on the sides of the DIMM.
2.3.6.3
Removing a DDR2 DIMM
If you are returning the DIMM or the blade server for service, or if you are replacing
a DIMM with another DIMM, remove the DIMM from the Sun Netra CP3220 blade
server.
Note –
Safely store the original factory-shipped DIMM and related DIMM
packaging. Store any removed DIMM in the new DIMM packaging.
To remove a DIMM from the Sun Netra CP3220 blade server, perform the following
steps:
1. Access the blade server by performing one of the following procedures:
■
If the Sun Netra CP3220 blade server is installed in an ATCA shelf, remove the
blade server from the shelf as explained in
Section 2.3.3, “Removing the Sun
Netra CP3220 Blade Server” on page 2-18
.
■
Remove the Sun Netra CP3220 blade server from its antistatic envelope and place
it on an ESD mat near the ATCA shelf.
Summary of Contents for Sun Netra CP3220
Page 8: ...viii Sun Netra CP3220 Blade Server User s Guide January 2010...
Page 12: ...xii Sun Netra CP3220 Blade Server User s Guide January 2010...
Page 14: ...xiv Sun Netra CP3220 Blade Server User s Guide January 2010...
Page 34: ...1 16 Sun Netra CP3220 Blade Server User s Guide January 2010...
Page 78: ...3 8 Sun Netra CP3220 Blade Server User s Guide January 2010...
Page 94: ...4 16 Sun Netra CP3220 Blade Server User s Guide January 2010...
Page 117: ...Appendix B BIOS Screens B 3 FIGURE B 2 BIOS Main Menu FIGURE B 3 Advanced Configuration Menu...
Page 131: ...Appendix B BIOS Screens B 17...
Page 135: ...Index 4 Sun Netra CP3220 Blade Server User s Guide January 2010...