Sun Datacenter Switch 3456 Installation Guide • December 2008
FIGURE 6-2
Setting the Level
6. Note the position of the bubble.
7. Rotate the beam level 90 degrees, now running front to rear.
See
8. Note the position of the bubble.
9. Consider your next step:
■
If the bubble favored the right and the front, raise the right front foot or lower
the left rear foot.
■
If the bubble favored the right and the rear, raise the right rear foot or lower
the left front foot.
■
If the bubble favored the left and the front, raise the left front foot or lower the
right rear foot.
■
If the bubble favored the left and the rear, raise the left rear foot or lower the
right front foot.
10. Adjust the appropriate leveling foot.
11. Repeat
to
until the chassis is level.
■
If the adjustment causes a caster to lift from the floor, go to
■
If the adjustment causes a foot to lift from the floor, go to .
■
Otherwise, go to
.