Chapter 11
Cabling the Switch
103
1. Locate the cable connector at iPASS connector 12B.
This cable is the upper cable.
2. Grasp the cable connector to support its weight and apply the removal force.
3. Pull on the loop of the retractor strap while simultaneously pulling on the
cable connector.
The cable connector comes free.
4. Carefully move the cable out of the front branch of the cable tree.
5. Gently lower the cable so that is it hanging from the side branch.
Caution –
Do not allow the cable to drop or strike the floor. Jerking, bending,
pulling on, or dropping the cable will damage the cable. See
6. Repeat from
for the cable at iPASS connector 12A.
This cable is the lower cable.
7. Repeat from
moving to the right for cables at iPASS connectors 13B, 13A,
14B, and so on to 23A.
8. Repeat from
moving to the left for cables at iPASS connectors 11B, 11A,
10B, and so on to 0A.
▼
To Check Link Status
1. Access the CMC as described in
Summary of Contents for Datacenter Switch 3456
Page 10: ...x Sun Datacenter Switch 3456 Installation Guide December 2008 ...
Page 14: ...xiv Sun Datacenter Switch 3456 Installation Guide December 2008 ...
Page 20: ...6 Sun Datacenter Switch 3456 Installation Guide December 2008 ...
Page 48: ...34 Sun Datacenter Switch 3456 Installation Guide December 2008 ...
Page 49: ...Chapter 5 Unpacking the Chassis 35 ...
Page 73: ...58 Sun Datacenter Switch 3456 Installation Guide December 2008 ...
Page 87: ...72 Sun Datacenter Switch 3456 Installation Guide December 2008 ...
Page 97: ...82 Sun Datacenter Switch 3456 Installation Guide December 2008 ...
Page 125: ...110 Sun Datacenter Switch 3456 Installation Guide December 2008 ...