36
Sun Datacenter Switch 3456 Installation Guide • December 2008
■
Check the elevators in path, if any.
2. Verify that the leveling feet are in the fully raised position.
3. With one person as the pusher and at least one other person as a guider, begin
moving the chassis on the path.
Caution –
The guider can cross to either side of the chassis, but should never
remain in the path of motion.
4. Move the chassis as slow as reasonably possible.
Note –
When approaching intersections, doorways, or places where interaction with
others or collision might occur, announce your presence.
5. When you arrive at the final location, position the chassis for leveling and
securing.
▼
To Level the Chassis
Once the chassis is at the final location, you must level the chassis. The chassis does
not need to be perfectly level. However, the load borne by the casters should now be
distributed between the casters and the leveling feet.
Note –
The directions indicated in this procedure are referenced from the front or
line card side of the chassis.
1. Position the Sun Datacenter Switch 3456 in the final location.
2. Using the adjustable wrench, lower the first leveling foot so that it contacts the
floor and you begin to feel resistance.
See
Summary of Contents for Datacenter Switch 3456
Page 10: ...x Sun Datacenter Switch 3456 Installation Guide December 2008 ...
Page 14: ...xiv Sun Datacenter Switch 3456 Installation Guide December 2008 ...
Page 20: ...6 Sun Datacenter Switch 3456 Installation Guide December 2008 ...
Page 48: ...34 Sun Datacenter Switch 3456 Installation Guide December 2008 ...
Page 49: ...Chapter 5 Unpacking the Chassis 35 ...
Page 73: ...58 Sun Datacenter Switch 3456 Installation Guide December 2008 ...
Page 87: ...72 Sun Datacenter Switch 3456 Installation Guide December 2008 ...
Page 97: ...82 Sun Datacenter Switch 3456 Installation Guide December 2008 ...
Page 125: ...110 Sun Datacenter Switch 3456 Installation Guide December 2008 ...