25
Section 6
SUPERVISOR PROTOCOL
3- P3 pressure in psig
4- P4 pressure in psig
5- T1 temperature in deg F
6- T2 temperature in deg F
7- T3 temperature in deg F
8- T4 temperature in deg F
9- T5 temperature in deg F
10- eConnect ID number
11- Analog Shutdown (0 on Supervisor)
12- Digital Outputs
13- Digital Shutdown (0 on Supervisor)
14- Digital inputs
15- Total run time in hours
16- Total load time in hours
17- Run Status (See DATA TYPES)
18- Mode (See DATA TYPES)
Q – Quick Status Request
##Qxx
01Q4E
Monitor request for data from slave controllers. Slave responds with q message type.
q – Quick Status Response
##q19,2,15,17,18xx
01q0,115,2000,M,C65
Controller’s response of quick status. Data fields are:
19- Capacity in cfm
2- P2 pressure in psig
23- Sequence hours
17- Run Status (See DATA TYPES)
18- Mode (See DATA TYPES)
G – Get parameter Request
##G22,xx
01G3,F9
Monitor’s request to change a parameter. The controller responds with g message type.
22- Parameter number (See DATA TYPES)
g – Get parameter Response
##g22,21xx
01g3,4A5
The controller’s response to a valid message type G request.
22- Parameter number (See DATA TYPES)
21- Value of the parameter (See DATA TYPES )
P – Put parameter Request
##P22,21,xx
01P3,4,90
Monitor’s request to change a parameter. The controller responds with p message type.
22- Parameter number (See DATA TYPES)