Section 3
SPECIFICATIONS
9
3.1 SPECIFICATIONS
COMPRESSOR POWER RANGE:
200-450HP/ 149-335KW
FAN DIAMETER:
42” (200-250HP/ 149-186KW)
48” (300-450HP/ 224-336KW)
FAN POWER:
71/2HP (REMOTE) (200HP)/900RPM/AOPE
10HP (INTEGRAL) (250HP)/1200RPM/AOPE
15HP (300-350HP)/900RPM/AOPE
20HP (400-450HP)/1200RPM/AOPE
TEMPERATURE CONTROLLERS:
Electrical:
120VAC Input/24VAC Output 50/60HZ
Enclosure:
Nema 1
Mixed Air Range:
10º to 90ºF (-12º to 32ºC)
Outdoor Air Changeover Range:
20º to 90ºF (-6º to 32ºC)
ROOM THERMOSTAT:
Electrical:
120VAC
Range:
40º to 90ºF (4º to 32ºC)
Solenoid Valve:
Electrical:
120VAC/60HZ
Enclosure:
Nema 1
AIR VOLUME
(at listed Water Gauge Duct Restriction):
18,000 CFM- 200HP/149KW
30,000 CFM- 250-350HP/186-261KW
35,000 CFM- 400-450HP/298-336KW
Allowable ductwork pressure drop is 0.5 w.g. static maximum for all horsepowers listed. A booster
fan is required if pressure drop exceeds 0.5 w.g.
Summary of Contents for EES LS25S Series
Page 18: ...Section 4 INSTALLATION 14 Table 2 Ductwork Static Pressure Loss Worksheet ...
Page 20: ...NOTES 16 ...
Page 26: ...NOTES 22 ...
Page 58: ...Section 6 ILLUSTRATIONS AND PARTS LIST 54 6 14 DECAL GROUP ...
Page 60: ...Section 6 ILLUSTRATIONS AND PARTS LIST 56 6 15 DECAL LOCATIONS ...
Page 63: ...Section 6 ILLUSTRATIONS AND PARTS LIST 59 6 17 WIRING DIAGRAM EES REMOTE 02250134 081R00 ...
Page 65: ...NOTES 61 ...