Section 2
DESCRIPTION
5
2.1 INTRODUCTION
The Sullair Integral Heat Recovery System is a
means of recovering energy which is expended
while producing compressed air. This energy can
be converted into a usable source of heat. The heat
is stored in the compressor cooling air as it passes
over the compressor motor, fluid cooler and after-
cooler. The compressor cooling air can then be
used as preheated make-up air or heating air for
plants, warehouses, etc. Heat may also be rejected
from the system when it is not required.
Any make-up air introduced into a heating or ven-
tilation system by this system must be of breath-
ing air quality as defined by applicable codes,
laws or regulations.
Because the heat recovery system is built into the
compressor package it requires a minimal amount
of installation labor. The system has been
designed so that use of auxiliary blowers is not
needed as long as good duct design is practiced
(See
Figure 2-1 Sullair Heat Recovery System- Typical Overview
Summary of Contents for EES LS25S Series