PRODUCT USER MANUAL
SECTION 2
16
2.17 STEPS TO UNDERTAKE
BEFORE OPERATING
1. Read this manual completely.
2. Review all safety precautions.
3. Use recommended pipe sizes as per specifi-
cations.
4. DO NOT operate the dryer at pressures
above the maximum specified on the dryer
label (check the technical specifications).
5. DO NOT operate the dryer in temperatures
above 120°F / 50°C degrees
6. DO NOT operate the dryer with inlet air tem-
peratures above 150°F / 65°C.
2.18 OPERATING PROCEDURES
This procedure should be followed on first start-up,
after periods of extended shutdown or following
maintenance procedures. Qualified personnel must
perform the start-up.
S
EQUENCE
OF
OPERATIONS
1. Ensure that all the steps of the “Installation”
chapter have been observed.
2. Ensure that the connection to the com-
pressed air system is correct and that the
piping is suitably fixed and supported.
3. Ensure that the condensate drain pipe is
properly fastened and connected to a collec-
tion system.
4. Ensure that the by-pass system (if installed)
is closed and the dryer is isolated.
5. Ensure that the manual valve of the conden-
sate drain circuit is open.
6. Remove any packaging and other material
which could obstruct the area around the
dryer.
7. Activate the mains switch.
8. Turn on the main switch - pos. 1 on the con-
trol panel.
9. Check that the mains power light of the ON/
OFF button is ON.
10. Wait at least two hours before starting the
dryer (compressor crankcase heater must
heat the oil of the compressor)
11. Ensure the cooling water flow and tempera-
ture is adequate (Water-Cooled).
12. Switch ON the dryer pressing the button "I -
ON" of the ON/OFF switch on the digital con-
troller
13. Ensure the data plate flow rate match with
plant consumption.
14. If the dryer does not start to run check the
monitor on the Microprocessor. If the Phase
error is mentioned on the screen change the
Phases and re-start the dryer.
15. Allow the dryer temperature to stabilize 10-
15 minutes
16. Slowly open the air inlet valve.
17. Slowly open the air outlet valve.
18. Slowly close the central by-pass valve of the
system (if optional By-pass valves are
installed).
19. Check the piping for air leakage.
20. Ensure the drain is regularly cycling - wait for
its first interventions.
Summary of Contents for 02250201-297 R01
Page 6: ...TABLE OF CONTENTS ...
Page 8: ...8 NOTES ...
Page 38: ...38 NOTES ...
Page 39: ...Section 4 39 TECHNICAL DRAWINGS ...
Page 40: ...SECTION 4 40 4 1 ED SPARE PARTS RD400 AIR COOLED 02250196 586 R03 ...
Page 42: ...SECTION 4 42 4 2 ED SPARE PARTS RD500 AIR COOLED 02250196 588 R03 ...
Page 44: ...SECTION 4 44 4 3 ED SPARE PARTS RD700 AIR COOLED 02250196 590 R3 ...
Page 46: ...SECTION 4 46 4 4 ED SPARE PARTS RD700 WATER COOLED 02250196 618 R03 ...
Page 48: ...SECTION 4 48 4 5 ED SPARE PARTS RD850 AIR COOLED 02250196 591 R03 ...
Page 50: ...SECTION 4 50 4 6 ED SPARE PARTS RD850 WATER COOLED 02250196 619 R03 ...
Page 52: ...SECTION 4 52 4 7 ED SPARE PARTS RD1000 AIR COOLED 02250196 592 R03 ...
Page 54: ...SECTION 4 54 4 8 ED SPARE PARTS RD1000 WATER COOLED 02250196 620 R03 ...
Page 56: ...SECTION 4 56 4 9 ED SPARE PARTS RD1200 AIR COOLED 02250196 593 R03 ...
Page 58: ...SECTION 4 58 4 10 ED SPARE PARTS RD1200 WATER COOLED 02250196 621 R03 ...
Page 60: ...SECTION 4 60 4 11 ED SPARE PARTS RD1600 AIR COOLED 02250196 594 R03 ...
Page 62: ...SECTION 4 62 4 12 ED SPARE PARTS RD1600 WATER COOLED 02250196 622 R03 ...
Page 64: ...SECTION 4 64 4 13 ED SPARE PARTS RD2000 AIR COOLED 02250196 595 R03 ...
Page 66: ...SECTION 4 66 4 14 ED SPARE PARTS RD2000 WATER COOLED 02250196 623 R03 ...
Page 68: ...SECTION 4 68 4 15 ED SPARE PARTS RD2400 AIR COOLED 02250196 596 R03 ...
Page 70: ...SECTION 4 70 4 16 ED SPARE PARTS RD2400 WATER COOLED 02250196 624 R03 ...
Page 72: ...SECTION 4 72 4 17 ED SPARE PARTS RD3000 AIR COOLED 02250196 597 R03 ...
Page 74: ...SECTION 4 74 4 18 ED SPARE PARTS RD3000 WATER COOLED 02250196 625 R03 ...
Page 76: ...SECTION 4 76 4 19 ED SPARE PARTS RD3800 AIR COOLED 02250196 598 R03 ...
Page 78: ...SECTION 4 78 4 20 ED SPARE PARTS RD3800 WATER COOLED 02250196 626 R03 ...
Page 80: ...SECTION 4 80 4 21 ED SPARE PARTS RD5000 AIR COOLED 02250196 599 R03 ...
Page 82: ...SECTION 4 82 4 22 ED SPARE PARTS RD5000 WATER COOLED 02250196 627 R03 ...
Page 84: ...SECTION 4 84 4 23 ED SPARE PARTS RD6000 AIR COOLED 02250196 600 R03 ...
Page 86: ...SECTION 4 86 4 24 ED SPARE PARTS RD6000 WATER COOLED 02250196 628 R03 ...
Page 88: ...SECTION 4 88 4 25 ID RD400 02250195 264 ...
Page 90: ...SECTION 4 90 4 26 ID RD500 850 02250195 266 ...
Page 92: ...SECTION 4 92 4 27 ID RD1000 1200 02250195 267 R01 ...
Page 94: ...SECTION 4 94 4 28 ID RD1600 2000 02250195 268 ...
Page 96: ...SECTION 4 96 4 29 ID RD2400 02250195 269 ...
Page 98: ...SECTION 4 98 4 30 ID RD3000 02250195 269 ...
Page 100: ...SECTION 4 100 4 31 ID RD3800 02250195 270 ...
Page 102: ...SECTION 4 102 4 32 ID RD5000 02250195 271 ...
Page 104: ...SECTION 4 104 4 33 ID RD6000 02250195 272 ...
Page 106: ...SECTION 4 106 4 34 P I RD400 02250195 291 ...
Page 108: ...SECTION 4 108 4 35 P I RD500 850 02250195 293 ...
Page 110: ...SECTION 4 110 4 36 P I RD700 850 WATER COOLED 02250195 294 ...
Page 112: ...SECTION 4 112 4 37 P I RD1000 6000 02250195 297 ...
Page 114: ...SECTION 4 114 4 38 P I RD1000 6000 WATER COOLED 02250195 298 ...
Page 116: ...SECTION 4 116 4 39 WIRING DIAGRAM RD400 230 3 60 A 02250195 319 S1 ...
Page 118: ...SECTION 4 118 4 39 WIRING DIAGRAM RD400 230 3 60 A 02250195 319 S2 ...
Page 120: ...SECTION 4 120 4 40 WIRING DIAGRAM RD400 460 3 60 A 400 3 50 A 02250195 974 S1 ...
Page 122: ...SECTION 4 122 4 40 WIRING DIAGRAM RD400 460 3 60 A 400 3 50 A 02250195 974 S2 ...
Page 124: ...SECTION 4 124 4 41 WIRING DIAGRAM RD500 700 230 3 60 A 02250195 975 S1 ...
Page 126: ...SECTION 4 126 4 41 WIRING DIAGRAM RD500 700 230 3 60 A 02250195 975 S2 ...
Page 132: ...SECTION 4 132 4 43 WIRING DIAGRAM RD700 850 230 3 60 W 02250195 976 S1 ...
Page 134: ...SECTION 4 134 4 43 WIRING DIAGRAM RD700 850 230 3 60 W 02250195 976 S2 ...
Page 144: ...144 NOTES ...
Page 145: ...NOTES ...