© STULZ GmbH, Hamburg
4
5.3 Remote installation
Use the kit code VSDBAS0000 for the remote wall-mounted installation of the ventilated steam
distributor. The kit consists of a support frame for the distributor, to be fastened to the wall, as shown in
Fig. 5.4 .
The kit consists of a support frame for the distributor, to be fastened to the wall, as shown in Fig. 5.5 .
Procedure (with reference to Figures 5.4 and 5.5)
1. Make three holes in the wall as shown in Fig. 5.4 or using the remote
support as a drilling template: make sure that the two holes at the ends are
horizontal, so as to ensure level installation.
2. Fasten the remote support to the wall using the screws and anchors supplied.
3. After having established the chosen path, cut the steam pipe Ø
inner
30 mm
and the condensate drain pipe Ø
inner
= 7 mm to measure.
4. Remove the protective guard from the distributor (see Chap. 4).
5. Connect the condensate drain pipe to the special fitting inside the
distributor.
6. Connect the steam pipe to the fitting inside the distributor and fasten it
by using one of the supplied clamps.
7. Connect the supplied supply cable to the “X1-X2” clamp on the side
of the ventilated steam distributor.
8. Rest the distributor on the support, fastening the drain pipe to connection “G´ ”
and passing the steam pipe through hole “A”.
9. Remove the front cover from the humidifier (see the humidifier manual)
10. Make a Ø= 40 mm hole in the closing gasket “A” located on top of the humidifier
(see Fig. 5.3).
11. Insert the steam pipe through the hole in gasket „A“ of the humidifier and connect it to the steam outlet on
the cylinder; then fasten it to the cylinder by using the 2
nd
supplied clamp.
12. Connect the condensate drain pipe to connection “D” on the support.
13. Connect the free end of the condensate drain pipe to connection “G”, which is located on the top of the
humidifier (see Fig. 5.5) or to the waste water drain.
14. Insert the power cable in the hole “B” and connect it to the clamps ”X1“ and „X2“.
15. Fasten the distributor to the support by using two self-threading plastic screws, placed in holes “C´ “.
16. Replace the protective guard on the distributor (see Chap. 4).
17. Replace the front cover on the humidifier (see the humidifier manual).
min. 70
0
61
,5
28
Ø 6
165,9
66,2
114
Ø 6
Ø 6
Wall drilling template (distances in mm)
Fig. 5.4
14
Fig. 5.5
Proper installation of the ventilated steam distributor and the steam and condensate drain pipes is
essential for the correct operation of the appliance.
IMPORTANT WARNING:
EN
Summary of Contents for SEH0053H40E2
Page 2: ...STULZ GmbH Hamburg 2...
Page 12: ...STULZ GmbH Hamburg 7...