5 Assembling the ventilated steam distributor
5.1 Positioning
The steam distributor may be fitted to the top of the humidifier (Fig. 5.1) or alternatively positioned
separately (Fig. 5.2) and connected to the humidifier by a steam pipe, which can be ordered separately:
In both cases, the following rules have to be regarded:
a) The path of the steam pipe must exploit gravity to drain the condensate steam back to the
humidifier; pockets or traps must be avoided, as the condensate may accumulate there and the
pipe must not be chocked due to sharp bends or twisting.
b) The length of the steam pipe from the humidifier to the distributor must be less than 4 metres.
c) Figures 5.1 and 5.2 indicate the minimum recommended distances to prevent the humidified air
flow from coming into direct contact with people, electrical equipment, false ceilings and cold
surfaces before the steam has been absorbed by the environment.
5.2 Installation on top of the humidifier
1. Remove the front cover of the humidifier (see the humidifier manual).
2. Remove cap A from the top of the humidifier.
3. Remove the protective guard from the ventilated distributor (see Chap. 4)
4. Connect one end of the steam pipe to the distributor inlet and fasten it
by using one of the supplied clamps.
5. Connect the condensate drain pipe to the special fitting inside the distributor.
6. Connect the supplied supply cable to the “X1-X2“ clamp on the side of the
ventilated steam distributor.
7. Place the ventilated steam distributor on top of the humidifier, inserting the
steam pipe into hole “A” and connect the condensate drain pipe to fitting “G”.
8. Cut the steam supplied steam pipe to measure (see Table 5.1)
9. Using the 2
nd
clamp supplied, fasten the steam pipe to the steam outlet on
the humidifier cylinder.
10. Fasten the distributor to the top of the humidifier by using the two
self-threading plastic screws, placed in the holes “C”.
11. Carry the supply cable through bore “B” and connect it to the “X1” and “X2” clamp of the humidifier.
12. Replace the protective guard on the ventilated steam distributor and the front cover on the humidifier.
Model
SEH0053 … 0083
H40E2
SEH0103 … 0153 H40E2
Capacity [kg/h]
5,0 … 8,0
10,0 … 15,0
Length [mm]
225
225
Table 5.1
Dimensions in
m
A >
0,5
B >
5
C
≥
2,1
D
≥
1
Dimensions in
m
A >
0,5
B >
5
C
≥
1
D
≤
4
Fig. 5.1
Fig. 5.2