Symptom
Probable Cause
Recommendation
Head Pressure Too
High
Low condenser airflow. (Indicated
by excessive warm air leaving the
condenser fan).
Open air passages.
Clean coil.
Check condenser fan(s).
Air or other non-condensable gas
in system
Reclaim system and recharge. Install a new drier strainer.
Overcharge of refrigerant
Reclaim excess refrigerant from system
Condenser fan not on.
Check main voltage power source to unit.
Check fan, contactor, fan cycling switch or fan speed
controller
Erratic Fan Operation
Dirty or blocked condenser coil.
Clean coil or remove blockage