Series GEN 2 Ultrasonic Humidifier IOM Manual
Atomized mist is visible from the mist outlet.
Check the
humidifier
parts, supply water piping and drain piping for signs of leaking water.
Check to see that the mist diffusion is good and no obstacles are directly exposed to the mist.
CAUTION
Do not block the outlet of the mist; component failure could occur.
Precautions
1.
Do not operate the
humidifier
when no air
fl
ow is present to move the mist out of the
humidifier.
2.
Do not remove the mist guide cover from the
humidifier during
operation.
3.
For sanitary reasons, drain the water from the tank
if the humidifier is turned off for more
than 3 days.
Steps for Long Term Shutdown
If the humidifier is not signaled to turn On for a period of three days, the Level
Controller will automatically
signal the humidifier to initiate a drain cycle.
When operation is stopped for a long time (one week or longer), the following steps must be performed.
Also, refer to General Maintenance section.
1. Close the water supply valve.
2. Drain the water tank.
3. Set the main power switch on the control box to Off.
4.
Check and clean the water tank interior.
To restart operation after a long-term shutdown, see the Procedure for Operation section