Stulz CyberRow CRS-090-C Engineering Manual Download Page 9

9

Chilled Water

24” Chilled Water

CRS-180-C

Total Capacity 

Sensible Capacity 

Flow Rate 

GPM 

Total System 

Pressure Drop, 

Ft. H

2

BTU/H

kW

BTU/H

kW

100

˚

FDB/ 69.2

˚

FWB Entering Air Temperature

40

˚

F EWT

10

˚

T

263,192

77.1

250,429

73.3

54.5

39.4

12

˚

T

251,539

73.7

245,539 71.9

43.5

26.8

45

˚

F EWT

10

˚

T

219,854

64.4

219,854

64.4

45.9

29.2

12

˚

T

211,927

62.1

211,927

62.1

37.0

20.2

50

˚

F EWT

10

˚

T

192,259

56.3

192,259

56.3

40.5

23.4

12

˚

T

186,556

54.6

186,556

54.6

32.8

16.5

95

˚

FDB/67.7

˚

FWB Entering Air Temperature

40

˚

F EWT

10

˚

T

242,729

71.1

227,717

66.7

50.5

34.8

12

˚

T

230,726

67.6

222,663

65.2

40.1

23.3

45

˚

F EWT

10

˚

T

199,089

58.3

199,089

58.3

41.8

24.9

12

˚

T

190,287

55.7

190,287

55.7

33.4

17.0

50

˚

F EWT

10

˚

T

170,772

50.0

170,772

50.0

36.2

19.4

12

˚

T

164,228

48.1

164,228

48.1

29.0

13.4

90

˚

FDB/66.1

˚

FWB Entering Air Temperature

40

˚

F EWT

10

˚

T

221,108

64.7

204,623

59.9 46.2

29.8

12

˚

T

207,922

60.9 199,053

58.3

36.2

19.6

45

˚

F EWT

10

˚

T

177,357

51.9

177,357

51.9

37.4

20.3

12

˚

T

167,355

49.0

167,355

49.0

29.5

14.0

50

˚

F EWT

10

˚

T

148,407

43.5

148,407

43.5

31.6

15.4

12

˚

T

141,408

41.4 141,408

41.4

25.2

10.8

85

˚

FDB/64.5

˚

FWB Entering Air Temperature

40

˚

F EWT

10

˚

T

199,491

58.4

180,880

53.0

41.8

25.0

12

˚

T

184,737

54.1

174,604

51.1

32.4

16.3

45

˚

F EWT

10

˚

T

154,771

45.3

154,771

45.3

32.9

16.7

12

˚

T

144,039

42.2

144,039

42.2

25.6

11.1

50

˚

F EWT

10

˚

T

125,357

36.7

125,357

36.7

27.0

12.1

12

˚

T

117,882

34.5

117,882

34.5

21.3

8.5

80

˚

FDB/62.8

˚

FWB Entering Air Temperature

40

˚

F EWT

10

˚

T

176,442

51.7

156,565

45.8

37.2

20.6

12

˚

T

159,804

46.8

149,444

43.8

28.2

13.0

45

˚

F EWT

10

˚

T

130,953

38.3

130,953

38.3

28.2

12.9

12

˚

T

119,742

35.1

119,742

35.1

21.6

8.7

50

˚

F EWT

10

˚

T

101,625

29.8

101,625

29.5

22.3

9.0

12

˚

T

93,093

27.3 93,093

27.3

17.1

6.3

PERFORMANCE DA

TA

Summary of Contents for CyberRow CRS-090-C

Page 1: ...1 STULZ CyberRow Engineering Manual Engineering Manual EM 13 77 kW Chilled Water Row Based Data Center Cooling Utilizing EC Fan Technology 60 Hz Data Indoor Cooling Row...

Page 2: ...utstanding customer service make STULZ the perfect choice for all your environmental control needs ISO 9001 Quality Registered STULZ is committed to satisfying customer expectations by meeting and exc...

Page 3: ...nclature 4 CyberRow Features 5 Configurations 6 Technical Data 7 Performance Data 8 Electrical and Sound Data 10 Dimensional Data 11 Standard Product Features 13 Product Guide Specifications 14 Chille...

Page 4: ...4 MODEL NOMENCLATURE CyberRow Row Based System Nominal Capacity in 1 000 of BTU H CyberRow System Chilled Water System CRS 180 C CyberRow...

Page 5: ...nd infinitely adjustable EC fans ensure maximum efficiency Used in containment open architecture and hot spot reduction applications Adapts to both high and low density IT environments Wide range of c...

Page 6: ...om mixing with cool air The front of IT equipment is accessed in the external cold aisle The Stulz CyberRow draws the contained hot air from the hot aisle removes the heat and supplies cooled air into...

Page 7: ...ntity of Blowers 3 3 Drive Method Direct Direct Humidification Electrode Steam Canister Humidifier with Adjustable Output Optional Lbs Hr kW Input N A 5 1 7 Std Control N A Proportional Washable Filte...

Page 8: ...5 80 417 23 5 13 7 6 8 90 FDB 66 1 FWB Entering Air Temperature 40 F EWT 10 F T 108 988 31 9 108 988 31 9 22 1 14 0 12 F T 103 324 30 3 103 324 30 3 17 5 9 7 45 F EWT 10 F T 96 139 28 2 96 139 28 2 19...

Page 9: ...3 4 90 FDB 66 1 FWB Entering Air Temperature 40 F EWT 10 F T 221 108 64 7 204 623 59 9 46 2 29 8 12 F T 207 922 60 9 199 053 58 3 36 2 19 6 45 F EWT 10 F T 177 357 51 9 177 357 51 9 37 4 20 3 12 F T 1...

Page 10: ...51 4 53 6 51 7 45 0 30 6 58 4 54 Fan Speed Airflow SCFM CRS 180 C Sound Pressure LpA free field dBA in a 146 91 ft 4 16m room at 3 28 ft 1 0m distance 50 4100 29 4 42 5 46 6 48 6 52 3 52 5 41 5 26 1 5...

Page 11: ...NNECTION POWER CONNECTION AIR OUT AIR OUT AIR IN AIR IN POWER POWER CONNECTIONS CONNECTIONS PIPING PIPING CONNECTIONS CONNECTIONS CONDENSATE CONDENSATE CONNECTION CONNECTION POWER POWER CONNECTIONS CO...

Page 12: ...Panel Option HUMIDIFIER HUMIDIFIER CONNECTIONS CONNECTIONS POWER POWER CONNECTIONS CONNECTIONS PIPING PIPING CONNECTIONS CONNECTIONS CONDENSATE CONDENSATE CONNECTION CONNECTION AIR IN AIR IN AIR OUT...

Page 13: ...Valve Optional Optional Electrode Steam Canister Humidifier N A Optional ELECTRICAL SYSTEM 16 Automatic Dual Power Transfer Switch Optional Optional Remote Stop Start Contacts Standard Standard Main...

Page 14: ...fins with enhanced fin design for maximum heat transfer and STULZ CyberRow 13 77 kW Row Based Precision Control Air Conditioners Chilled Water Systems SUMMARY This specification describes requirements...

Page 15: ...e loop and be securely fastened by an approved method Each wire in the unit shall be numbered for ease of service tracing All electrically actuated components shall be easily accessible from the front...

Page 16: ...ult and their ranges shall be easily viewed and adjusted from the user interface display The program and operating parameters shall be permanently stored on a non volatile system in the event of power...

Page 17: ...operate using the setpoints programmed by the factory The customer may enter new operating parameters in the Control menu and the system will then operate accordingly The new setpoints may be stored a...

Page 18: ...be factory supplied and shall ship separately for field installation Upon sensing a water leak the normally closed water detector control circuit shall open thereby shutting down the CyberRow unit s w...

Page 19: ...19 Chilled Water NOTES...

Page 20: ...m STULZ Air Technology Systems Inc 1572 Tilco Drive Frederick Maryland 21704 Phone 301 620 2033 Fax 301 662 5487 E mail info stulz ats com www STULZ com STULZ mission is to be the premier provider of...

Reviews: