Stulz CyberRow CRS-090-C Engineering Manual Download Page 16

rotating parts.  Each high voltage circuit shall be individually 
protected by circuit breakers or manual motor starters on 
all three phases. The blower motor shall have thermal and 
short circuit protection. Line voltage and 24 volt control 
circuit wiring shall be routed in separate bundles. The 
electric box shall include all the contactors, starters, fuses, 
circuit breakers and terminal boards required for operation 
of the CyberRow® unit and shall allow for full service via 
front and rear access panel.

AUTOMATIC DUAL POWER TRANSFER 
SWITCH (OPTIONAL)

Two individual main power input disconnect switches shall 
be provided, one for each incoming power source. In the 
event the primary power fails or a phase loss/imbalance 
occurs, the automatic transfer switch transfers power to the 
secondary power source. Once the primary power has been 
restored, the transfer switch automatically shifts the power 
load back to the primary power. The transfer time from one 
source to the other is user adjustable to allow staging or 
sequence restart of load.

In addition to the automatic transfer switch function, the 
local controller display shall indicate which power source 
has failed. This indication is a visual depiction that allows 
the user to determine the status of the input source. 
This status can also be conveyed thru the BMS serial 
communication link.

REMOTE STOP/START CONTACTS

Included in the system’s electrical control circuit shall be 
a 2-pin terminal connection for remote stop/start of the 
CyberRow® air conditioner by remote source.

MAIN POWER SERVICE SWITCH

The CyberRow unit shall be provided with a unit mounted 
main power service switch.

16

 SERIES CONTROLLER DESCRIPTION

GENERAL

The advanced microprocessor based 

 

Series controller 

shall be equipped with fl exible software capable of meeting 
the specifi c needs of the application. The setpoints shall 
be default and their ranges shall be easily viewed and 
adjusted from the user interface display. The program and 
operating parameters shall be permanently stored on a 
non-volatile system in the event of power failure.

The controller shall be designed to manage temperature 
and relative humidity (RH) levels to a user defi ned setpoint 
via control output signals to the CyberRow® unit. Control 
parameters have variable outputs from 0 to 100% of the 
full rated capacity. 

The controller shall receive inputs for measurable control 
conditions (temperature, relative humidity, and dew point) 
via return air or room mounted sensors. The internal logic 
will then determine if the conditions require cooling, 
humidifi cation  or  dehumidifi cation.  Control  setpoints 
shall be established to maintain design conditions of 
the installation. The controller will respond accordingly 
to changes in these conditions and control the output/
demand for the appropriate mode of operation until user 
defi ned conditions are achieved.

FIELD CONFIGURABLE

The program for the 

 

Series controller shall be fi eld 

confi gurable, allowing the operator the capability of 
selecting control setpoints specifi c to the application. 
Operator interface for the 

 

controller is provided 

via a door mounted user interface display panel. The 
display panel shall have a backlit LCD graphical display 
and function keys giving the user complete control and 
monitoring capability of the precision cooling system. The 
menu driven interface shall provide users the ability to 
scroll through and enter various menu screens.

PASSWORD PROTECTION

Access to the Info Menu, Alarms Log, and the ability to 
monitor room conditions shall be allowed without the 
use of a password. Modifi cations to the control setpoints 
shall require the use of a password. The controller shall be 
programmed to recognize predetermined security levels 
before allowing access to display screens containing critical 
variables. Three secured menu levels (Control, Service 
and Factory) will support unique passwords that must be 

PRODUCT GUIDE SPECIFICA

TIONS

CyberRow®

Summary of Contents for CyberRow CRS-090-C

Page 1: ...1 STULZ CyberRow Engineering Manual Engineering Manual EM 13 77 kW Chilled Water Row Based Data Center Cooling Utilizing EC Fan Technology 60 Hz Data Indoor Cooling Row...

Page 2: ...utstanding customer service make STULZ the perfect choice for all your environmental control needs ISO 9001 Quality Registered STULZ is committed to satisfying customer expectations by meeting and exc...

Page 3: ...nclature 4 CyberRow Features 5 Configurations 6 Technical Data 7 Performance Data 8 Electrical and Sound Data 10 Dimensional Data 11 Standard Product Features 13 Product Guide Specifications 14 Chille...

Page 4: ...4 MODEL NOMENCLATURE CyberRow Row Based System Nominal Capacity in 1 000 of BTU H CyberRow System Chilled Water System CRS 180 C CyberRow...

Page 5: ...nd infinitely adjustable EC fans ensure maximum efficiency Used in containment open architecture and hot spot reduction applications Adapts to both high and low density IT environments Wide range of c...

Page 6: ...om mixing with cool air The front of IT equipment is accessed in the external cold aisle The Stulz CyberRow draws the contained hot air from the hot aisle removes the heat and supplies cooled air into...

Page 7: ...ntity of Blowers 3 3 Drive Method Direct Direct Humidification Electrode Steam Canister Humidifier with Adjustable Output Optional Lbs Hr kW Input N A 5 1 7 Std Control N A Proportional Washable Filte...

Page 8: ...5 80 417 23 5 13 7 6 8 90 FDB 66 1 FWB Entering Air Temperature 40 F EWT 10 F T 108 988 31 9 108 988 31 9 22 1 14 0 12 F T 103 324 30 3 103 324 30 3 17 5 9 7 45 F EWT 10 F T 96 139 28 2 96 139 28 2 19...

Page 9: ...3 4 90 FDB 66 1 FWB Entering Air Temperature 40 F EWT 10 F T 221 108 64 7 204 623 59 9 46 2 29 8 12 F T 207 922 60 9 199 053 58 3 36 2 19 6 45 F EWT 10 F T 177 357 51 9 177 357 51 9 37 4 20 3 12 F T 1...

Page 10: ...51 4 53 6 51 7 45 0 30 6 58 4 54 Fan Speed Airflow SCFM CRS 180 C Sound Pressure LpA free field dBA in a 146 91 ft 4 16m room at 3 28 ft 1 0m distance 50 4100 29 4 42 5 46 6 48 6 52 3 52 5 41 5 26 1 5...

Page 11: ...NNECTION POWER CONNECTION AIR OUT AIR OUT AIR IN AIR IN POWER POWER CONNECTIONS CONNECTIONS PIPING PIPING CONNECTIONS CONNECTIONS CONDENSATE CONDENSATE CONNECTION CONNECTION POWER POWER CONNECTIONS CO...

Page 12: ...Panel Option HUMIDIFIER HUMIDIFIER CONNECTIONS CONNECTIONS POWER POWER CONNECTIONS CONNECTIONS PIPING PIPING CONNECTIONS CONNECTIONS CONDENSATE CONDENSATE CONNECTION CONNECTION AIR IN AIR IN AIR OUT...

Page 13: ...Valve Optional Optional Electrode Steam Canister Humidifier N A Optional ELECTRICAL SYSTEM 16 Automatic Dual Power Transfer Switch Optional Optional Remote Stop Start Contacts Standard Standard Main...

Page 14: ...fins with enhanced fin design for maximum heat transfer and STULZ CyberRow 13 77 kW Row Based Precision Control Air Conditioners Chilled Water Systems SUMMARY This specification describes requirements...

Page 15: ...e loop and be securely fastened by an approved method Each wire in the unit shall be numbered for ease of service tracing All electrically actuated components shall be easily accessible from the front...

Page 16: ...ult and their ranges shall be easily viewed and adjusted from the user interface display The program and operating parameters shall be permanently stored on a non volatile system in the event of power...

Page 17: ...operate using the setpoints programmed by the factory The customer may enter new operating parameters in the Control menu and the system will then operate accordingly The new setpoints may be stored a...

Page 18: ...be factory supplied and shall ship separately for field installation Upon sensing a water leak the normally closed water detector control circuit shall open thereby shutting down the CyberRow unit s w...

Page 19: ...19 Chilled Water NOTES...