Stulz CyberRow CRS-090-C Engineering Manual Download Page 17

BMS INTERFACE

The 

 

series controller may incorporate a 10 Mbps 

 

communication interface port that can be fi eld connected 
through a serial interface to a Building Management 
System via Modbus, BACnet, SNMP, or HTTP as confi gured 
by the factory. A controller interfaced to a network must 
be confi gured for BMS communication.

ALARMS

Alarm conditions shall activate a red LED indicator that 
backlights the alarm function key. As an option, an alarm 
condition may also be enunciated by an audible alarm 
signal. An alarm is acknowledged by pressing the alarm 
key. This calls up alarm display screens that provide a text 
message detailing the alarm conditions.  After an alarm 
condition is corrected, the alarm can be cleared by pressing 
the alarm key.

SMALL BEZEL DISPLAY PANEL

The small bezel user interface display panel features an 
easy to read, backlit liquid-crystal alphanumeric display 
equipped with contrast adjustment and LED illuminated 
function keys. The screens that appear on the user 
interface display panel present data that originates from 
the controller I/O module. The controller is operated via a 
6-key menu-driven loop structure and offers an alarm log 
plus four different interface menu levels to the operator: 
Information, Control, Service, and Factory. These menus 
permit the user to easily view, control, and confi gure 
operating parameters for the CyberRow® unit.

OPTIONAL ACCESSORIES

MECHANICAL FLOW SWITCH (OPTIONAL)

  

A shipped loose fl ow switch shall activate a loss of fl ow 
alarm in the event of chilled water fl ow interruption.

DIFFERENTIAL TEMPERATURE 
FLOW (OPTIONAL)

A factory mounted and wired temperature sensor for inlet 
and outlet water temperatures shall permit a loss of fl ow 
alarm in the event the temperature difference is within 1° 
F (adjustable) during chilled water valve operation.

17

Chilled Water

entered to access the menu screens so only authorized 
personnel may perform modifi cations to the settings.

RESTORABLE PARAMETERS/FACTORY 
DEFAULTS

Upon initial start-up the CyberRow® system shall operate 
using the setpoints programmed by the factory. The 
customer may enter new operating parameters in the 
Control menu and the system will then operate accordingly. 
The new setpoints may be stored as, "Customer Default 
Setpoints". The primary setpoints entered by the factory 
still remain stored in the controllers’ memory as, "Factory 
Setpoints". The setpoints for the system may be re-
adjusted in the Control menu at any time. If it becomes 
necessary, the customer may restore the setpoints back 
to the Customer Default setpoint values or to the original 
Factory (primary) setpoint values.

TIMER FEATURE

The timer shall allow the user to set up an operating 
schedule to automatically scale back or shut down the air 
conditioner during low demand or unoccupied periods. 
This is an energy saving feature offering the user the ability 
to create an operating schedule tailored to the needs of the 
building. An evening (night-setback) schedule may also be 
created, allowing the CyberRow® unit to operate at night 
with relaxed temperature/humidity setpoints and offsets.

A/C GROUPING pLAN OPERATION

Multiple CyberRow® system controllers shall be able to be 
connected (grouped) to a pLAN local network, allowing 
the communication of data and information from each 
controller to a central control terminal or Lead controller. 
The Lead controller display screens can be used to monitor 
and adjust group control variables for the individual system 
controllers. Each 

 controller connected to the pLAN 

network shall be identifi ed with its own unique address. 

Multiple CyberRow® units consisting of up to eight 
STULZ precision air conditioners equipped with like 
controllers may be controlled and monitored via the E² 
series controller. With multiple CyberRow® units each 
unit can selectively be confi gured as “Active” to operate 
as a primary A/C, “Capacity Assist” for staged operation, 
or as “Standby” to come online in case of a failed air 
conditioning unit to ensure continuous availability. The 
controller may also be confi gured to rotate units with 
timed duty cycling to promote equal run-time and assure 
that each CyberRow® unit within the rotating group is 
operationally exercised on a periodic timed basis.

PRODUCT GUIDE SPECIFICA

TIONS

Summary of Contents for CyberRow CRS-090-C

Page 1: ...1 STULZ CyberRow Engineering Manual Engineering Manual EM 13 77 kW Chilled Water Row Based Data Center Cooling Utilizing EC Fan Technology 60 Hz Data Indoor Cooling Row...

Page 2: ...utstanding customer service make STULZ the perfect choice for all your environmental control needs ISO 9001 Quality Registered STULZ is committed to satisfying customer expectations by meeting and exc...

Page 3: ...nclature 4 CyberRow Features 5 Configurations 6 Technical Data 7 Performance Data 8 Electrical and Sound Data 10 Dimensional Data 11 Standard Product Features 13 Product Guide Specifications 14 Chille...

Page 4: ...4 MODEL NOMENCLATURE CyberRow Row Based System Nominal Capacity in 1 000 of BTU H CyberRow System Chilled Water System CRS 180 C CyberRow...

Page 5: ...nd infinitely adjustable EC fans ensure maximum efficiency Used in containment open architecture and hot spot reduction applications Adapts to both high and low density IT environments Wide range of c...

Page 6: ...om mixing with cool air The front of IT equipment is accessed in the external cold aisle The Stulz CyberRow draws the contained hot air from the hot aisle removes the heat and supplies cooled air into...

Page 7: ...ntity of Blowers 3 3 Drive Method Direct Direct Humidification Electrode Steam Canister Humidifier with Adjustable Output Optional Lbs Hr kW Input N A 5 1 7 Std Control N A Proportional Washable Filte...

Page 8: ...5 80 417 23 5 13 7 6 8 90 FDB 66 1 FWB Entering Air Temperature 40 F EWT 10 F T 108 988 31 9 108 988 31 9 22 1 14 0 12 F T 103 324 30 3 103 324 30 3 17 5 9 7 45 F EWT 10 F T 96 139 28 2 96 139 28 2 19...

Page 9: ...3 4 90 FDB 66 1 FWB Entering Air Temperature 40 F EWT 10 F T 221 108 64 7 204 623 59 9 46 2 29 8 12 F T 207 922 60 9 199 053 58 3 36 2 19 6 45 F EWT 10 F T 177 357 51 9 177 357 51 9 37 4 20 3 12 F T 1...

Page 10: ...51 4 53 6 51 7 45 0 30 6 58 4 54 Fan Speed Airflow SCFM CRS 180 C Sound Pressure LpA free field dBA in a 146 91 ft 4 16m room at 3 28 ft 1 0m distance 50 4100 29 4 42 5 46 6 48 6 52 3 52 5 41 5 26 1 5...

Page 11: ...NNECTION POWER CONNECTION AIR OUT AIR OUT AIR IN AIR IN POWER POWER CONNECTIONS CONNECTIONS PIPING PIPING CONNECTIONS CONNECTIONS CONDENSATE CONDENSATE CONNECTION CONNECTION POWER POWER CONNECTIONS CO...

Page 12: ...Panel Option HUMIDIFIER HUMIDIFIER CONNECTIONS CONNECTIONS POWER POWER CONNECTIONS CONNECTIONS PIPING PIPING CONNECTIONS CONNECTIONS CONDENSATE CONDENSATE CONNECTION CONNECTION AIR IN AIR IN AIR OUT...

Page 13: ...Valve Optional Optional Electrode Steam Canister Humidifier N A Optional ELECTRICAL SYSTEM 16 Automatic Dual Power Transfer Switch Optional Optional Remote Stop Start Contacts Standard Standard Main...

Page 14: ...fins with enhanced fin design for maximum heat transfer and STULZ CyberRow 13 77 kW Row Based Precision Control Air Conditioners Chilled Water Systems SUMMARY This specification describes requirements...

Page 15: ...e loop and be securely fastened by an approved method Each wire in the unit shall be numbered for ease of service tracing All electrically actuated components shall be easily accessible from the front...

Page 16: ...ult and their ranges shall be easily viewed and adjusted from the user interface display The program and operating parameters shall be permanently stored on a non volatile system in the event of power...

Page 17: ...operate using the setpoints programmed by the factory The customer may enter new operating parameters in the Control menu and the system will then operate accordingly The new setpoints may be stored a...

Page 18: ...be factory supplied and shall ship separately for field installation Upon sensing a water leak the normally closed water detector control circuit shall open thereby shutting down the CyberRow unit s w...

Page 19: ...19 Chilled Water NOTES...

Page 20: ...m STULZ Air Technology Systems Inc 1572 Tilco Drive Frederick Maryland 21704 Phone 301 620 2033 Fax 301 662 5487 E mail info stulz ats com www STULZ com STULZ mission is to be the premier provider of...

Reviews: