The humidifi er assembly shall include integral fi ll cup, fi ll 
and drain valves and associated piping.

The canister shall be designed to collect the mineral 
deposits in the water and provide clean particle free steam 
to the air stream, thereby reducing maintenance cost.

The microprocessor control shall maintain humidifi er 
operation through fi ll and drain cycles based on the water 
conductivity. Overfl ow and loss of fl ow protection shall be 
provided along with a manual drain switch. A high water 
alarm with built-in time delay shall provide an indication 
to change canister. The humidifi cation system shall require 
no cleaning maintenance during the cylinder life. 

The humidifi er shall discharge steam at 212 degrees F. 
and atmospheric pressure. It shall be capable of operating 
with water in the range of 200 to 1500 micromhos. The 
steam shall be introduced into the air stream, after the 
evaporator, by a calibrated discharge tube designed to 
equally distribute the steam to the air stream without 
condensation. The humidifi er shall have a capacity of 5 
Lbs/hr.

A factory wired and installed humidifi er drain pump shall 
be installed.  This pump is designed to operate with the 
higher condensate temperatures caused by the fl ush 
and drain cycle of the electrode canister humidifi ers. 
The humidifi er drain line will be connected to the main 
condensate line prior to exiting the cabinet.

DEHUMIDIFICATION CYCLE

The CyberRow® unit shall be provided with a 
dehumidifi cation control mode. During dehumidifi cation 
demand, the control mode shall permit chilled water 
valve operation and EC motor speed control to condense 
moisture on the cooling coil.

ELECTRICAL SYSTEM

The electrical system shall conform to National Electrical 
Code (NEC) requirements. In accordance with NEC Class II 
circuits, the control circuit shall be 24 volts AC and control 
circuit wiring shall not be smaller than 18 AWG.  All wiring 
shall be neatly wrapped, run in conduit or cable trays, and 
routed in bundles. Each wire shall end with a service loop 
and be securely fastened by an approved method. Each 
wire in the unit shall be numbered for ease of service 
tracing.

All electrically actuated components shall be easily 
accessible from the front and rear of the unit without 
reaching over exposed high voltage components or 

15

Chilled Water

mounted in a stainless steel condensate drain pan. The 
coil shall be designed for a maximum of 500 ft./min. face 
velocity. The water circuit shall be designed to distribute 
water into the entire coil face area.

PIPING CONFIGURATION

Top Piping:

   When top piping is specifi ed, the CyberRow® 

units shall be provided with connections for both the 
chilled water piping and condensate discharge on the top 
of the cabinet.

Bottom Piping:

  When bottom piping is specifi ed  (e.g. 

raised fl oor applications), the CyberRow® units shall be 
provided with connections for both chilled water piping 
and condensate pump discharge on the bottom of the 
cabinet.

CONDENSATE PUMP

The CyberRow® shall include a factory wired and installed 
in-pan condensate pump.  The condensate pump shall 
have the capacity of 3 gal/hr. at 3 ft. of lift with a maximum 
shut off (head) of 40 ft.  The condensate pump shall be 
piped with either top or bottom discharge connections to 
remain consistent with top or bottom chilled water piping 
connections.

2-WAY (STANDARD)

A 2-way modulating valve rated for a maximum 400 psig 
w.w.p. shall be factory piped and wired. The 2-way chilled 
water modulating valve shall automatically meter the 
fl ow of chilled water to the cooling coil in response to a 
proportional signal (0-10 VDC) provided to the valve by the 
microprocessor controller w.w.p.

3-WAY (OPTIONAL)

The water circuit shall include a factory mounted, 3-way 
modulating (0 - 10 VDC) control valve. Design pressure 
shall be 400 psig.

STEAM GENERATING HUMIDIFIER 
(OPTIONAL FOR 24” CABINET DESIGN)

The humidifi er shall be of a self-contained steam generating 
electrode type, utilizing a plastic disposable cylinder with 
full probes, connected to electric power via cylinder plugs 
that slide onto the electrode pins. The electrode pins shall 
be constructed from expanded low carbon steel, zinc 
plated, and dynamically formed for precise current control. 

PRODUCT GUIDE SPECIFICA

TIONS

Summary of Contents for CyberRow CRS-090-C

Page 1: ...1 STULZ CyberRow Engineering Manual Engineering Manual EM 13 77 kW Chilled Water Row Based Data Center Cooling Utilizing EC Fan Technology 60 Hz Data Indoor Cooling Row...

Page 2: ...utstanding customer service make STULZ the perfect choice for all your environmental control needs ISO 9001 Quality Registered STULZ is committed to satisfying customer expectations by meeting and exc...

Page 3: ...nclature 4 CyberRow Features 5 Configurations 6 Technical Data 7 Performance Data 8 Electrical and Sound Data 10 Dimensional Data 11 Standard Product Features 13 Product Guide Specifications 14 Chille...

Page 4: ...4 MODEL NOMENCLATURE CyberRow Row Based System Nominal Capacity in 1 000 of BTU H CyberRow System Chilled Water System CRS 180 C CyberRow...

Page 5: ...nd infinitely adjustable EC fans ensure maximum efficiency Used in containment open architecture and hot spot reduction applications Adapts to both high and low density IT environments Wide range of c...

Page 6: ...om mixing with cool air The front of IT equipment is accessed in the external cold aisle The Stulz CyberRow draws the contained hot air from the hot aisle removes the heat and supplies cooled air into...

Page 7: ...ntity of Blowers 3 3 Drive Method Direct Direct Humidification Electrode Steam Canister Humidifier with Adjustable Output Optional Lbs Hr kW Input N A 5 1 7 Std Control N A Proportional Washable Filte...

Page 8: ...5 80 417 23 5 13 7 6 8 90 FDB 66 1 FWB Entering Air Temperature 40 F EWT 10 F T 108 988 31 9 108 988 31 9 22 1 14 0 12 F T 103 324 30 3 103 324 30 3 17 5 9 7 45 F EWT 10 F T 96 139 28 2 96 139 28 2 19...

Page 9: ...3 4 90 FDB 66 1 FWB Entering Air Temperature 40 F EWT 10 F T 221 108 64 7 204 623 59 9 46 2 29 8 12 F T 207 922 60 9 199 053 58 3 36 2 19 6 45 F EWT 10 F T 177 357 51 9 177 357 51 9 37 4 20 3 12 F T 1...

Page 10: ...51 4 53 6 51 7 45 0 30 6 58 4 54 Fan Speed Airflow SCFM CRS 180 C Sound Pressure LpA free field dBA in a 146 91 ft 4 16m room at 3 28 ft 1 0m distance 50 4100 29 4 42 5 46 6 48 6 52 3 52 5 41 5 26 1 5...

Page 11: ...NNECTION POWER CONNECTION AIR OUT AIR OUT AIR IN AIR IN POWER POWER CONNECTIONS CONNECTIONS PIPING PIPING CONNECTIONS CONNECTIONS CONDENSATE CONDENSATE CONNECTION CONNECTION POWER POWER CONNECTIONS CO...

Page 12: ...Panel Option HUMIDIFIER HUMIDIFIER CONNECTIONS CONNECTIONS POWER POWER CONNECTIONS CONNECTIONS PIPING PIPING CONNECTIONS CONNECTIONS CONDENSATE CONDENSATE CONNECTION CONNECTION AIR IN AIR IN AIR OUT...

Page 13: ...Valve Optional Optional Electrode Steam Canister Humidifier N A Optional ELECTRICAL SYSTEM 16 Automatic Dual Power Transfer Switch Optional Optional Remote Stop Start Contacts Standard Standard Main...

Page 14: ...fins with enhanced fin design for maximum heat transfer and STULZ CyberRow 13 77 kW Row Based Precision Control Air Conditioners Chilled Water Systems SUMMARY This specification describes requirements...

Page 15: ...e loop and be securely fastened by an approved method Each wire in the unit shall be numbered for ease of service tracing All electrically actuated components shall be easily accessible from the front...

Page 16: ...ult and their ranges shall be easily viewed and adjusted from the user interface display The program and operating parameters shall be permanently stored on a non volatile system in the event of power...

Page 17: ...operate using the setpoints programmed by the factory The customer may enter new operating parameters in the Control menu and the system will then operate accordingly The new setpoints may be stored a...

Page 18: ...be factory supplied and shall ship separately for field installation Upon sensing a water leak the normally closed water detector control circuit shall open thereby shutting down the CyberRow unit s w...

Page 19: ...19 Chilled Water NOTES...

Page 20: ...m STULZ Air Technology Systems Inc 1572 Tilco Drive Frederick Maryland 21704 Phone 301 620 2033 Fax 301 662 5487 E mail info stulz ats com www STULZ com STULZ mission is to be the premier provider of...

Reviews: