The economizing damper signal shall allow a minimum output
setting for minimum outside air control to meet ventilation
requirements.
Exhaust relief is not included and must be provided by others
to prevent over-pressurizing the controlled space.
BMS Interface (Optional)
The STULZ
E²
series controller shall incorporate a 10 Mbps
communication interface port that can be fi eld connected
through a serial interface to a Building Management System
via Modbus, BACnet, SNMP, or HTTP as configured by
the factory. A controller interfaced to a network must be
confi gured for BMS communication.
STULZ
E²
Constant Contact (Optional)
The control package shall include a STULZ Constant Contact
short term power supply for the STULZ
E²
series controller
to allow the controller to manage the power transfer switch
from one primary power source to another while maintaining
communications with an active monitoring system. The
E²
Constant Contact shall permit a minimum of one minute
ride thru period. The Constant Contact shall include LED
indications for presence of power, low charge indication, and
minimum backup time.
SAFETY
FEATURES
Smoke Detection (Optional)
A photo-electric smoke detector shall be factory installed
and wired in the return air section of the CyberPack system.
The photo-electric detector shall include built-in circuitry
that performs a functional test of all detection circuits at
least once every 40 seconds without the need for generating
smoke. The UL listed velocity range shall be 0-3000 fpm. The
air conditioner shall shut down upon sensing smoke in the
return air stream.
Firestat (Optional)
The air conditioner shall be provided with a factory mounted
and wired firestat. The firestat shall shut down the air
conditioner upon sensing air temperatures that indicate a fi re.
Remote Water Detector: Spot Type
(Optional)
A remote single-point water and leak detector shall be factory
supplied and shall ship separately for fi eld installation. Upon
sensing a water leak, the normally-closed water detector
control circuit shall open, thereby shutting down the
CyberPack system’s water producing components.
Remote Water Detector: Dual Spot Type
(Optional)
Quantity 2-(two) remote single point water/leak detector
shall be factory supplied and shall ship separately for fi eld
installation. Upon sensing a water leak, the normally-closed
water detector control circuit shall open, thereby shutting
down the CyberPack's water producing components.
Remote Water Detector: Strip Type
(Optional)
A 20 foot (6 m) long remote strip/cable-type water and
leak detector shall be provided for remote fi eld installation.
Upon sensing a water leak, the normally-closed water
detector control circuit shall open, thereby shutting down
the CyberPack system’s water producing components.