All functions of the air conditioner shall be controlled by 
a factory installed STULZ 

 Series controller. The control 

program shall be specifi c to the air conditioner and include 
user-adjustable setpoints and tuning.  STULZ 

 Controller 

includes supply and return temp/RH sensors shipped loose.

 Series Controller Description

General

The advanced microprocessor based STULZ 

 series 

controller shall be equipped with fl exible software capable of 
meeting the specifi c needs of the application. The setpoints 
shall be default and their ranges shall be easily viewed and 
adjusted from the user interface display. The program and 
operating parameters shall be permanently stored on a non-
volatile system in the event of power failure.

The controller shall be designed to manage temperature and 
relative humidity (RH) levels to a user defi ned setpoint via 
control output signals to the DX system. 

The controller shall receive inputs for measurable control 
conditions (temperature, relative humidity, and dew point) 
via return air or room mounted sensors. The internal logic 
shall then determine if the conditions require cooling or 
dehumidifi cation. Control setpoints shall be established to 
maintain design conditions of the installation. The controller 
shall respond accordingly to changes in these conditions and 
control the output/demand for the appropriate mode of 
operation until user defi ned conditions are achieved.

Field Confi gurable

The program for the STULZ 

 series controller shall be fi eld 

confi gurable, allowing the operator the capability of selecting 
control setpoints specific to the application. Operator 
interface for the STULZ 

 Controller is provided via a user 

interface display panel. The display panel shall have a backlit 
LCD graphical display, and function keys, giving the user 
complete control and monitoring capability of the precision 
cooling system. The menu driven interface shall provide users 
the ability to scroll through and enter various menu screens.

Password Protection

Access to the Info Menu, Alarms Log, and the ability to 
monitor room conditions shall be allowed without the use of a 
password.  Modifi cations to the control setpoints shall require 
the use of a password. The controller shall be programmed 
to recognize predetermined security levels before allowing 
access to display screens containing critical variables. Three 
secured menu levels (Control, Service and Factory) shall 
support unique passwords that must be entered to access 

the menu screens so only authorized personnel may perform 
modifi cations to the settings.

Restorable Parameters/Factory Defaults

Upon initial start-up, the air conditioning system shall operate 
using the setpoints programmed by the factory. The customer 
may enter new operating parameters in the control menu and 
the system shall then operate accordingly. The new setpoints 
may be stored as, "Customer Default Setpoints". The primary 
setpoints entered by the factory still remain stored in the 
controller's memory as "Factory Setpoints". The setpoints 
for the system may be re-adjusted in the Control menu at 
any time. If it becomes necessary, the customer may restore 
the setpoints back to the Customer Default setpoint values 
or to the original Factory (primary) setpoint values.  

Alarms

Alarm conditions shall activate a red LED indicator that 
backlights the alarm function key. As an option, an alarm 
condition may also be enunciated by an audible alarm signal.  
An alarm is acknowledged by pressing the alarm key. This 
calls up alarm display screens that provide a text message 
detailing the alarm conditions. After an alarm condition is 
corrected, the alarm can be cleared by pressing the alarm key.

Small Bezel Display Panel

The small bezel user interface display panel features an easy 
to read, backlit liquid-crystal alphanumeric display equipped 
with contrast adjustment and LED illuminated function 
keys. The screens that appear on the user interface display 
panel present data that originates from the controller I/O 
module. The controller is operated via a 6-key menu-driven 
loop structure and offers an alarm log plus four different 
interface menu levels to the operator: Information, Control, 
Service, and Factory. These menus permit the user to easily 
view, control, and confi gure operating parameters for the 
air conditioning unit. 

Air-Side Economizer (Optional)

The CyberPack system shall be equipped with a unique 
air-side economizer for applications utilizing outdoor Air-
Side Economizing. The STULZ Air-Side Economizer package 
shall include return air and outside air dampers, outdoor 
temperature and humidity sensor, remote space return 
air sensor, and supply air sensor for proper control during 
economizer operation. Control settings shall be included for 
both temperature and humidity properties of the outdoor air. 
A damper signal lockout shall be included if the outdoor air 
conditions reach user adjustable limits. 

Summary of Contents for CyberPack ASC-12C

Page 1: ...ditioner Pa a a a ag g d d R Ro oo o t t p p A Ai i o on nd d o o e e Outdoor Cooling Engineering Manual Air Conditioner EM STULZ CyberPack Systems Packaged Rooftop Air Conditioner 42 105 kW Self Contained Precision Air Conditioner Utilizing EC Fan Technology ...

Page 2: ...asonic Humidifiers Duct AHU Wall Mounted Stand alone Clean Energy Efficient Evaporative Cooling Precision Air Conditioning Ceiling Row Floor Mounted from 1 200 tons Air Water Glycol Chilled Water Free Cooling Alternate Water Source ISO 9001 Quality Registered STULZ is committed to satisfying customer expectations by meeting and exceeding requirements Our Quality Policy ensures that every Employee ...

Page 3: ...ta Technical Specifications Electrical Data FLA MCA MFS 4 Dimensional Data Installation Drawings ASC 12C 13C 15C DX 5 ASC 20A 25A 30A DX 6 Guide Specifications Product Guide Specifications 7 10 Table of Contents CyberPack Air Conditioner Systems CONDENSER FANS COMPRESSORS RECEIVERS EVAPORATOR FAN S EVAPORATOR COILS GALVANNEALED STEEL BASE FILTERS FRESH AIR INLET CONDENSATE PAN CyberPack Interior V...

Page 4: ... with up to 12 000 CFM nominal airflow CyberPack direct expansion refrigerant systems utilize multiple independent refrigerant circuits each packaged with an air cooled condensing unit as the primary cooling source CyberPack units are also available with optional air side economizer cooling STULZ E2 series controller stages refrigerant circuits and or dampers and manages fan speed as needed to pre...

Page 5: ...iet Operation Low noise scroll compressors coupled with EC fans and acoustically lined cabinets provide quiet operation Non Proprietary Parts CyberPack systems incorporate non proprietary components where possible Most major HVAC refrigeration and electrical distributors stock an exact model cross reference or an alternate to most factory provided components Rugged Design CyberPack systems are con...

Page 6: ...ction with microchannel fins The condensing units are equipped with high efficiency EC axial fans The fans utilize corrosion resistant multi blade impellers designed for high aerodynamic efficiency which results in lower power consumption lower noise levels and longer life Microchannel Condenser Coils Microchannel coils are constructed of brazed aluminum high performance fins to provide low air si...

Page 7: ...rd Standard Refrigerant Sight Glasses Filter Drier Strainers Standard Standard AIR COOLED CONDENSER Microchannel Coils Standard Standard Flooded Head Pressure Control with Receivers Rated Down to 30 F Ambient Standard Standard Axial Fans with EC Motors Standard Standard SUPPLY FANS MOTORS Backward Inclined Plenum Style Fan With an EC Motor Standard Standard ELECTRICAL 3 Phase Power Supply See Elec...

Page 8: ... 2 2 Evaporator Coil Rows 4 4 4 4 4 4 Face Area 15 6 15 6 15 6 23 8 23 8 23 8 Scroll Compressors Number of Scroll Compressors 2 2 2 2 2 2 Condenser Fans Nominal Power each Condenser Fan 3 8 3 8 3 8 3 8 3 8 3 8 Quantity 2 2 2 4 4 4 Filter Nominal Size H x W x D 20 x 20 x 4 20 x 20 x 4 20 x 20 x 4 20 x 20 x 4 20 x 20 x 4 20 x 20 x 4 Quantity 6 6 6 8 8 8 Condensate Drain in MPT 3 4 2 3 4 2 3 4 2 3 4 ...

Page 9: ...e Economizer operation requires exhaust air relief to be provided by others 104 3 BASE 57 2 74 1 147 3 104 3 BASE 68 9 BASE 57 2 147 3 FRESH AIR INLET REMOVABLE LIFTING LUG 4 PLACES RETURN AIR INLET 62 9 x 20 9 SUPPLY AIR OUTLET 55 5 x 28 5 SUPPLY AIR OUTLET 55 5 x 28 5 ECONOMIZER OUTSIDE AIR INLET REMOVABLE LIFTING LUG 4 PLACES 171 3 74 1 68 9 BASE RETURN AIR INLET 62 9 x 20 9 ...

Page 10: ... BASE 57 2 88 0 150 0 119 0 BASE 82 8 BASE 57 2 88 0 150 0 FRESH AIR INLET SUPPLY AIR OUTLET 69 4 x 28 1 Note Economizer operation requires exhaust air relief to be provided by others SUPPLY AIR OUTLET 69 4 x 28 1 ECONOMIZER OUTSIDE AIR INLET 174 0 REMOVABLE LIFTING LUG 4 PLACES RETURN AIR INLET 76 8 x 21 9 REMOVABLE LIFTING LUG 4 PLACES RETURN AIR INLET 76 8 x 21 9 ...

Page 11: ...experience in the design and fabrication of similar equipment CABINET The CyberPack unit cabinet shall be constructed of formed 5052 grade aluminum for corrosion protection The cabinet shall be of formed sections welded and ground smooth The exterior shall be finished with a weather and UV resistant coating Unit air leakage shall be less than 1 of design airflow rate measured at rated unit static ...

Page 12: ...roll Compressor The compressors shall be a high efficiency high reliability and low noise scroll compressor The compressor shall be complete with internal vibration isolation internal thermal overloads an internal pressure relief valve an internal discharge gas vibration eliminator and external vibration mounting isolation Snap Acting Hot Gas Bypass Optional The CyberPack system shall incorporate ...

Page 13: ...o display screens containing critical variables Three secured menu levels Control Service and Factory shall support unique passwords that must be entered to access the menu screens so only authorized personnel may perform modifications to the settings Restorable Parameters Factory Defaults Upon initial start up the air conditioning system shall operate using the setpoints programmed by the factory...

Page 14: ... system The photo electric detector shall include built in circuitry that performs a functional test of all detection circuits at least once every 40 seconds without the need for generating smoke The UL listed velocity range shall be 0 3000 fpm The air conditioner shall shut down upon sensing smoke in the return air stream Firestat Optional The air conditioner shall be provided with a factory moun...

Page 15: ...11 Packaged Rooftop Air Conditioner Notes ...

Page 16: ...oduction Facilities U S A Germany Italy China India ISO 9001 Quality Management System Requirements ISO9001 Registered Quality System STULZ Air Technology Systems Inc 1572 Tilco Drive Frederick Maryland 21704 Phone 301 620 2033 Fax 301 662 5487 E mail info stulz ats com www STULZ USA com February 2016 QENA019 Specifications subject to change without notice ...

Reviews: