System control to ensure the hygienic requirements
The air conditioning system must be checked in the specified intervals according to table 1 to ensure the
hygienic requirements.
No.
Task
Eventual
measure
Required interval in calendar months
1
3
6
12 24 hyg. control
1
Housing
1.1
Check on fouling at the air intake and outlet, damage
and corrosion
Cleaning and
repair
X
2
Air filter
2.1
Check on contamination and damage
Exchange the
corresponding
filters
X
2.2
Check of differential pressure
Filtertausch
X
2.3
Inspection of the hygienic state
X
3
Fan section
3.1
Check on fouling, damage and corrosion
Cleaning and
repair
X
3.2
Cleaning the air conducting fan parts, as well as the
condensate drain
X
4
Heat exchanger
4.1
Check on fouling, damage and corrosion
Cleaning and
repair
X
4.2
Check of fouling, corrosion and function of the con
-
densate tray
X
4.3
Check of fouling and function of the siphon
X
4.4
Inspection of the hygienic state
X
Table 1: check list