35
M03
Ma01
Ma02
M04
Ot01
Ot15
M05
Df01
Df07
M06
Co01
Co21
M01
M02
Pa01
Pa04
Pb01
Pb05
Pc01
Pc14
Ea01
Ea09
Eb01
Eb09
Ec01
P. Plus Menu* config.
EVO Menu* config.
© STULZ Gmbh – all rights reserved EN/02.2018/G17F
cyberlab original inSTrUcTionS
Here the BMS settings must be selected. The serial Modbus address of the
µPC is set on 001 as standard and has not to be changed. In the C7000IOC
however, the command "icc 1 id 1" must be entered to enable a communication.
The baudrate must be set on 9600.
Here the used compressor must be adjusted. The compressor type can be
seen on the type plate of the compressor.
SIAM ANB33-400V
or
SIAM ANB66-400V
SIAM ANB42-400V
or
SIAM ANB78-400V
SIAM ANB52-400V
(Set default: Yes) By this setting the inverter is initialized suitably to the com-
pressor . It is compellingly required to select "Yes". Following, the data is written
in the inverter.
The program verifies the compatibility of compressor and inverter, displays the
result of the verification in Wz04a and requires the confirmation for writing the
default setting.
Write default: Yes
After the confirmation with the ENTER key, the display shows "Wait default
install", then the value for "Write default" switches back to "No".
By ESC you get back to view Wz04.
Scroll to view Wz08 with the "down arrow" key.
Confirm the configuration with "Yes".
Menu structure
On the following pages some settings
will be changed in the views Pc09,
Co04, Co05, Co08, Co14, Co15,
Ea02 and Eb02.
The menu structure helps you to find
these windows.
nOte