23
h
p = -300Pa
3 cm
>10 cm
© STULZ GmbH – all rights reserved EN/02.2018/G17F
cyberlab original instructions
If the height h is smaller than 3 cm with a pressure of 300
Pa in the suction area, a water column remains in the drain,
the water does not drain off and fills the fan pan. This
water can be drawn dropwise in the fan or can drop out of
the unit through the panels if the pan is full.
unit limit
possible installation at the custo-
mer side: funnel
InFORMAtIOn
Comply with the regulations of the local water
supply authority.
Connect the condensate water drains to the local waste
water system.