11. Options
11.1 Raised floor stand
The floor stand is used to adjust the height of the chiller to the existing raised floor and consists of an encir-
cling rectangular profile of galvanized steel with adjustable screw sockets. Anti vibration compound is recom-
mended between concrete floor and base plate.
Locating the supports
Cabinet size
B
mm
Supports
n°
Rectangular profiles 70x40
n°
Mafund strips
n°
Screws M8x30
n°
Mounting
Raised floor stand
X/Y = Opening in raised floor
Z = Limit of distance
• A concrete foundation is recommended in the
area of the raised floor supports.
• If the floor stand is placed near a wall, a minimum
distance of 50 mm must be respected. The gap
between wall and floor stand must be closed by
tin stripes.
• Choose the dimensions of the openings in the
raised floor (X and Y) 10 mm longer than the
raised floor stand dimensions.
• Close the joint with a continuous seal.
• The raised floor cutting (notch) should at
least be 15° and must not have any contact
to the raised floor stand, which could result in
bone-conduction.
• Install the raised floor supports on vibration
dampening material (Mafund plate) (do not screw
down the supports!).
• Prior to installation of the chiller, install the raised
floor 7 mm higher than the raised floor plates, as
the mafund plates are compressed by the weight
of the chiller.