22
Kältemittel
R410A
Niederdruckschalter
Auslösung bei
bar
3,0
automatischer Reset bei
bar
6,0
Hochdruckschalter
Auslösung bei
bar
36
Manueller Reset möglich bei
bar
29
Sicherheitsventil
Auslösung bei
bar
40
EN/09.2017/G44 © STULZ GmbH – all rights reserved
cybercool indoor chiller original instructions
Refrigerant
low pressure switch
releases at
bar
automatic reset at
bar
High pressure switch
releases at
bar
manual reset possible at
bar
Safety valve
releases at
bar
Setting of the pressure switches and safety valve:
Design conditions
Electrical connection:
400V / 3ph+N+PE / 50Hz
Chilled water circuit:
Cooling medium:
Water, 0 % glycol
Entering water temperature:
18 °C
Leaving water temperature:
12 °C
Temperature constance:
± 2 K
Refrigerant circuit:
Condensation temperature:
50 °C
max. condensation temperature:
55 °C
Cooling medium circuit:
Cooling medium:
Water, 30 % glycol
Medium inlet temperature (DX):
39 °C
Medium outlet temperature (DX):
45 °C
Medium inlet temperature (FC):
10 °C
Medium outlet temperature (FC):
15 °C