![Stulz CyberCool 2 CQO 1102 ASF Original Instructions Manual Download Page 79](http://html1.mh-extra.com/html/stulz/cybercool-2-cqo-1102-asf/cybercool-2-cqo-1102-asf_original-instructions-manual_1387304079.webp)
79
max.
115
mm
min.
80
mm
© STULZ GmbH – all rights reserved EN/09.2019/G42
cybercool 2 scroll original insTrUcTions
Mounting
The easiest way to mount the anti-vibration mounts is to lift the chiller approximately 1.5 m above the ground
and keep it at this height while you fix the mounts.
• The lower nut should be at the same height for all mounts.
• Mark the position in advance on the threaded rod.
• Then attach the anti-vibration mount, in accordance with the drawing below.
• Keep in mind that the anti-vibration mounts under load yield up to 4 mm in height.
• Now position the chiller on the provided support frame and fasten the anti-vibration mounts on this frame.
nut
washer
washer
nut
Size 5 - 7:
Size 7
Size 6½
Size 6
Size 5