Air Handlers Units
ClimaPac Series
Verifi cations/ previous actions
Task type
Description
Comments
Filters
Previous check
•
They are clean, without visible damage and no foreign body prevents the good circulation of
air,
•
They are correctly fi xed to the frame.
Integrated control
Previous check
•
Electrical connections are correctly made with the appropriate supply voltage and the
earthing is made,
Casing
Previous check
•
Panels and profi les are clean and without visible damage,
•
There are no loose objects inside the unit that could damage the components or the casing
when the fans start.
•
Roof is properly installed (units for outdoor installation).
Coils venting
Water coils are provided with venting screws, located on the outlet header.
Venting screw
Coil Draining
Venting of coil
5.2
First start
Before starting the fans, make sure all the doors are closed and the dampers are open.
If the unit is equipped with a controller, consult the controller user’s instructions before starting the
unit (in separate document).