Level
User
ref.
Parameter
Unit
12
24
48
Mod.
value
Factory
Min
Max
Factory
Min
Max
Factory Min
Max
Expert
1262
Power level 2 (AUX 1)
% Pnom
80
20
120
80
20
120
80
20
120
Expert
1263
Time delay 2 (AUX 1)
min
5
0
60
5
0
60
5
0
60
Expert
1264
Inverter power level 3 activate (AUX 1)
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1265
Power level 3 (AUX 1)
% Pnom
50
20
120
50
20
120
50
20
120
Expert
1266
Time delay 3 (AUX 1)
min
30
0
60
30
0
60
30
0
60
Expert
1267
Inverter power level to deactivate (AUX 1)
% Pnom
40
20
120
40
20
120
40
20
120
Expert
1268
Time delay to deactivate (AUX 1)
min
5
0
60
5
0
60
5
0
60
Inst.
1503
Contact active according to battery temperature
(AUX 1) With BSP or BTS
Inst.
1446
Contact activated with the temperature of
battery (AUX 1)
No/Yes
No
-
-
No
-
-
No
-
-
Inst.
1447
Contact activated over (AUX 1)
°C
3
-10
50
3
-10
50
3
-10
50
Inst.
1448
Contact deactivated below (AUX 1)
°C
5
-10
50
5
-10
50
5
-10
50
Expert
1501
Contact active according to SOC (AUX 1) Only
with BSP
Expert
1439
Contact activated with the SOC 1 of battery
(AUX 1)
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1440
Contact activated below SOC 1 (AUX 1)
% SOC
50
0
100
50
0
100
50
0
100
Expert
1581
Delay 1 (AUX 1)
h
12
0
99
12
0
99
12
0
99
Expert
1582
Contact activated with the SOC 2 of battery
(AUX 1)
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1583
Contact activated below SOC 2 (AUX 1)
%
30
0
100
30
0
100
30
0
100
Expert
1584
Delay 2 (AUX 1)
h
0.2
0
99
0.2
0
99
0.2
0
99
Expert
1585
Contact activated with the SOC 3 of battery
(AUX 1)
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1586
Contact activated below SOC 3 (AUX 1)
%
20
0
100
20
0
100
20
0
100
Expert
1587
Delay 3 (AUX 1)
h
0
0
99
0
0
99
0
0
99
Expert
1441
Contact deactivated over SOC (AUX 1)
% SOC
90
0
100
90
0
100
90
0
100
Expert
1588
Delay to deactivate (AUX 1)
h
0.2
0
10
0.2
0
10
0.2
0
10
Expert
1589
Deactivate if battery in floating phase (AUX
1)
No/Yes
Yes
-
-
Yes
-
-
Yes
-
-
Expert
1512
Security, maximum time of contact (AUX 1)
No/Yes
No
-
-
No
-
-
No
-
-
Expert
1514
Maximum time of operation of contact (AUX 1)
min
600
10
1200
600
10
1200
600
10
1200
Expert
1569
Reset all settings (AUX 1)
-
-
-
-
-
-
-
-
-
Expert
1310
AUXILIARY CONTACT 2
Expert
1311
Operating mode (AUX 2)
Text
Reversed
automatic
-
-
Reversed
automatic
-
-
Reversed
automatic
-
-
Expert
1498
Combination of the events for the auxiliary
contact (AUX 2)
Text
Any (Function
OR)
-
-
Any
(Function
OR)
-
-
Any
(Function
OR)
-
-
Expert
1312
Temporal restrictions (AUX 2)
Expert
1313
Program 1 (AUX 2)