- 9 -
Cont ...
7.12
Stuart Turner gullies – cleaning procedure
It is recommended that the gully is cleaned at least every 3 months, to remove
hair, soap and scale deposit, as follows:
A more frequent maintenance may be required depending on usage.
This procedure covers all Stuart Turner gullies - images used for reference
only.
1. Using ‘Hook’ provided remove central Grille from
Gully, clean the Grill and rinse with fresh water
(Fig
12).
2. Using ‘Hook’ provided remove Sensor Cover
from Gully, clean the Cover and rinse with fresh
water (Fig 13).
3. Remove all debris from Gully and clean around
the Sensor switch, taking particular care around
the Sensor Switch Float to ensure no damage
occurs (Fig 14). Flush with clean fresh water.
4. Ensure the Sensor Switch Float is free to move
up / down on the Shaft.
5. If the Sensor Switch Float is stuck / not freely
moving, clean any detriment from the Shaft
ensuring no damage to the Shaft or Float occurs.
If scale is present this can be cleaned off using a
NON ACID based descalent. Flush with clean
fresh
water.
6. Re-assembly is the reverse of the instructions
above. Note the position of Sensor Cover
(Fig.
15).
7. Once re-assembled flush the Gully with clean
fresh water and check Pump System is operating
correctly.
8. If the Sensor Switch is damaged or not working please refer to the full
Shower Tray Pump Assembly instruction sheet for how to replace this part.
7.13
For Further Technical Support:
Phone the Stuart Turner PumpAssist team
on +44 (0) 844 98 000 97. Our staff are trained to help and advise you over the
phone.
Fig. 12
Fig. 13
Sensor hole must be
aligned with outlet
Sensor Switch Float
Fig. 15
Fig. 14