background image

- 16 -

Cont...

5 COMMISSIONING 

5.1 

IMPORTANT

 it is the responsibility of the installer to ensure that the Electrastream  

 

System is properly commissioned. Should the commissioning not be carried out, then  

 

the manufacturers guarantee and any extended warranty, will become null and void.

Wet System

5.2 

System flushing:

  The pipework system should be flushed out prior to the Electrastream  

 

being connected to ensure any contaminants/chemical residues and foreign bodies are  

 

removed from elsewhere in the system. 

5.3 

Expansion vessel pressure – hot water: (Cream vessel)

 

The air pressure should be set to 0.1 bar greater than the system pressure and must be  

 

set as part of the commissioning procedure.

 

Capacity        12 litres

 

If the hot water vessel needs to have its air charge checked or replenished, it should be  

 

carried out as follows: 

a)  Isolate unit electrically 

b)  Isolate water supply using the isolating valves 

c)  Release the system water pressure by opening a system outlet (tap) 

d)  Check air charge at Schrader valve (under the cap) using a tyre pressure gauge 

e)  Replenish air charge to suit the system if required by injecting air into the vessel via  

 

the Schrader valve using a car or bicycle pump, ensuring a system outlet valve  

 

remains open during this procedure to allow the vessel to exhaust any excess water. 

f)  Close all systems taps, open the isolating valves and turn on electrical power. 

g)  After the pressure has been changed, commission the unit see Section 5.5 onwards. 

5.4 

Expansion vessel pressure – heating system: (Grey vessel)

 

Maximum charge pressure 

  1.5 bar 

 

Maximum working temperature 

  90 °C 

 

Maximum Working Pressure  

  3 bar

 

Capacity 

  8 litres (for maximum system expansion of 7 litres)

 

The vessel pre charged is factory set to 1.9 bar, therefore it must be adjusted to suit the  

 

system before commissioning continues. 

 

The expansion vessel is supplied mounted on the unit, this is suitable for systems with a  

 

static head of up to 5 metres. If the static head is greater than 5 metres the charge  

 

pressure of the expansion vessel will need to be increased. Increase the pressure using a  

 

standard car tyre pump and pressure gauge when the system is empty (zero pressure). 

 

Expansion vessels are suitable for systems requiring a maximum expansion of 7 litres  

 

as detailed above. For systems requiring more expansion a second expansion vessel will  

 

be required. BS7074 Part 1 includes information on this requirement. 

 

Note: Normally expansion requirement is 4% of the system water content including the  

 

unvented cylinder coil 

5.5 

Hot water system pre-fill check:

 

a)  Check the hot water heating discharge pipes and tundish are correctly installed to  

 

conform to the Building Regulations G3. 

b)  Check all pipe connections are water tight. 

c)  Check the drain valve is closed. 

d)  If fitted, check that the Scale Protection Device or water softener has been fitted  

 

according to manufacturer’s instructions. 

5.6 

Filling hot water system:

a)  Open all shut off valves

b)  Open the incoming water isolating valve (mains stopcock) to the Electrastream and  

 

allow the unit to fill. 

c)  Open all domestic taps in turn to purge the air 

d)  Check system for leaks including around the Tri-Core heater. 

e)  Check no water is discharging from any relief valves. 

Summary of Contents for BEP 130

Page 1: ...ction booklet with the home owner as it contains important guarantee maintenance and safety information BEP 130 Pt No 46727 BEP 150 Pt No 46728 Read this manual carefully before commencing installatio...

Page 2: ...btu system suitable for flats apartments offices and other small dwellings STORAGE If this product is not to be installed immediately on receipt ensure that it is stored in a dry frost and vibration...

Page 3: ...ome into contact with any electrical device before the electrical supply is turned back on z z The Electrastream unit must be commissioned by a competant person failure to do so will invalidate the gu...

Page 4: ...removed from its packaging check for any damage prior to installation If any damage is found contact Altecnic Ltd within 24 hours of receipt Item Description Qty Item Description Qty Electrastream uni...

Page 5: ...ing cupboards and enclosed compartments Humidity may also present a problem within airing cupboards For servicing and cylinder replacement clearance is required all round the cylinder recommended 100...

Page 6: ...guarantee Higher water temperatures of 65 C and above can cause excessive scale The location and position of the water conditioner should be as per the manufacturer s recommendations 1 5 Check water p...

Page 7: ...ffs The valve must be set to suit the pressure of the system refer to the manufacturer s instructions 1 12 Room thermostat not supplied A standard room thermostat with no built in timers or functions...

Page 8: ...tor RCD MCB Cylinder TPR valve 6 bar Thermostatic mixing vlave Hot water outlet 22 mm connection Cold water supply 22 mm connection Combination valve including hot water PRV 6 bar Tundish Drain valve...

Page 9: ...outlets prior to the Electrastream connection Both of these connections are for 22 mm pipe 3 2 Heating system a The total output from the Electrastream for hot water and heating is 9 kW 240 V having...

Page 10: ...possible to and lower than the safety device with no more than 600 mm of pipe between the valve outlet and the tundish 3 5 The discharge pipe D2 The discharge pipe D2 from the tundish should Have a v...

Page 11: ...Contain a mechanical seal not incorporating a water trap which allows water into the branch pipe without allowing foul air from the drain to be ventilated through the tundish b Be a separate branch pi...

Page 12: ...ed for a straight length of 28 mm copper discharge pipe D2 from a G temperature relief valve is 18 m Subtract the resistance for 4 No 28 mm elbows at 1 0 m each 4 m Therefore the maximum permitted len...

Page 13: ...current and temperature rating for the requirements of the Electrastream as well as all other electrical requirements within the property It is advised to turn the switch off when hot water and heatin...

Page 14: ...d therefore only a mains cable not supplied is required to be installed through the cable gland located at the top of the RCD box This 3 core cable suitably sized is connected into the live neutral an...

Page 15: ...15 Cont Fig 10 Wiring diagram standard arrangement...

Page 16: ...system Grey vessel Maximum charge pressure 1 5 bar Maximum working temperature 90 C Maximum Working Pressure 3 bar Capacity 8 litres for maximum system expansion of 7 litres The vessel pre charged is...

Page 17: ...arth wiring has been installed correctly b Check tri core heater cover Electrastream controller cover and all other electrical covers are correctly fitted c Check tundish is positioned so that any spi...

Page 18: ...s failed see 5 17 HEAT 2 Indicates Eleement 2 is ON HEAT 2 Indicates heater element has failed see 5 17 HEAT 3 Indicates Eleement 3 is ON HEAT 3 Indicates heater element has failed see 5 17 VALVE Inid...

Page 19: ...19 Cont Fig 12 Electrastream control unit display settings For error displays see 8 1...

Page 20: ...within 2 of the set Target 65 C only one element will be on When the hot water is between 2 and 4 C below the set target then two elements will be on When the hot water within the cylinder is below 6...

Page 21: ...re within the cylinder becoming too high the TPR valve will vent The heating system has its own Pressure relief valve PRV and in the event of the pressure within the heating system becoming too high t...

Page 22: ...has to make special arrangements to the property s electrical supply to enable Electrastream to be used during both off peak and normal tariffs consult the installing electrician Boost can be used at...

Page 23: ...er functions 4 How to set room thermostat 5 The function of the Pressure Relief Valves and Combination valve and that over pressure will cause steam and scalding water to be emitted from the discharge...

Page 24: ...TPR valve and check that the water drains freely and safely to and from the tundish 10 Open combination PRV momentarily and close valve should shut off Repeat if valve sticks If valve will not shut o...

Page 25: ...ths this is done by pressing the RCD Test or T button this should switch the supply off Reset RCD to On after test If the RCD appears not to be working correctly contact your installer or a qualified...

Page 26: ...eat time t 60 o C 25 minutes 29 minutes Heat loss in 24 hrs 65 o C 0 97 kWh 1 06 kWh Heating System Expansion vessel size 8 litres Maximum system expansion 7 litres Expansion vessel pre charge pressur...

Page 27: ...setup Check timers and target temperature on Electrastream Control unit are set correctly Trip cut out Check over temperature cut out Reset system by switching heating and hot water OFF and allow for...

Page 28: ...hould not be run with all the radiators turned off unless there is a bypass valve in the system Check for air in the heating system Check that the cylinder temperature sensor has not been dislodged fr...

Page 29: ...water that complies with current at the time of installation EU standards and is not fed with water from a private source d The unit must not be modified in any way e Being subjected to excessive pres...

Page 30: ...30...

Page 31: ...31...

Page 32: ...Stuart Turner Ltd Henley on Thames Oxfordshire RG9 2AD ENGLAND Tel 44 0 1491 572655 Fax 44 0 1491 573704 info stuart turner co uk www stuart turner co uk Issue No 3619 1 02 Pt No 20908...

Reviews: