background image

31 

Integrated Electronic 

 Microprocessor Controller 

Read And Save These Instructions - Page 1 of 3 

Programming The Instrument 

 

To Modify The Setpoint 

 

 

Press and hold the “SET” key for at least 1 second. 

 

2. Use arrow keys 

 

 on temperature      

controller to increase (or decrease) the        
setpoint. 

 

3. Quickly press and release the “SET” key again. 

 

 

To Modify Defrost, Differential, Other Parameters 

 

1.  Press & hold “Prg” & “SET” keys together                                          
for five (5) seconds; display will flash “0”,                
representing password prompt. 

 

2. Confirm by pressing “SET” key. 

 

3. Press 

 or 

 to reach the 

category to be modified. 

 

 

4. Press “SET” to modify this selected parameter. 

 

 

5. Increase or decrease the value using 
the 

 or 

 button respectively. 

 

 

6. Press the “SET” key to temporarily save the new 
value and return to the display of the parameter. 

 

7. Press & hold the “Prg” key for at least 5 seconds 
to save changes.  This action will also mute the 
audible alarm (buzzer) & deactivate the alarm relay. 

 

Warning!  Save Your Parameter Settings! 

 

1.  To store the new parameter values, PRESS and HOLD the “Prg” key for at least 5 seconds.  
2.  All modifications made to parameters will be lost if you do NOT press a button within 60 seconds. Should 
this “timeout” occur, normal operational settings (prior to modifications being made) will resume. 
3.  If the instrument is switched off before pressing the “Prg” key, all modifications to parameters will be lost.   

Set 

Set 

 

aux 

Prg 

mute 

def 

 

Prg 

mute 

Set 

Set 

def 

 

Set 

 

aux 

 

aux 

def 

 

Set 

Prg 

mute 

Oper Manuals - PUB\Templates\Carel Controller\Carel Controller IR33.pub 

This data derived from Carel Material: ir33 +030220441 - rel. 2.0 - 01.05.2006

 

How To Change Reading From 

Fahrenheit (°F) To Celsius (°C) 

 

 

1. Press and hold “Prg” and “SET” keys 
together for at least 5 seconds; display 
will show “0” (password prompt). 

 

 

2. Confirm by pressing “SET” key. 

 

 

3. Press 

 or 

 until reaching the 

parameter “/ 5”. 

 

4. Press “SET” to modify this selected 
parameter. 

 

 

5. Press 

 or 

 to change value to 

desired setting: “0” for Celsius (°C) or 
“1” for Fahrenheit (°F). 

 

6. Press “SET” key to temporarily save the 
new value and return to the display of the 
parameter. 

 

7. Press & hold “Prg” key for at least 5 
seconds to save changes.  

Note!  All values 

will automatically convert to new scale.  No 
conversion is required.

 

Prg 

mute 

Set 

Set 

def 

 

 

aux 

Set 

 

aux 

def 

 

Set 

Prg 

mute 

Set 

def 

 

 

aux 

To Activate / Deactivate Auxiliary Output

  

 

Press and hold the “aux” key for 1 second.

 

 

aux 

To Activate Manual Defrost 

 

 Press and hold “def” key for at least 5 seconds. 

def 

 

To Reset Any Alarms With Manual 
Reset 

 

Press and hold the “Prg” and “aux”  

                    key for at least 1 second.

 

 

aux 

Prg 

mute 

Summary of Contents for CO35R

Page 1: ...ilar Design to Models CO35R CO45R and CO47R Model CO57R Shown With Optional Roll Down Security Door Similar Design to Models CO55R CO65R and CO67R MODEL CO35R 36 1 4 L x 33 1 4 D x 61 1 4 H MODEL CO45...

Page 2: ...S MAINTENANCE FUNDAMENTALS HONEYCOMB AIR DIFFUSERS MAINTENANCE FUNDAMENTALS SHELF ASSEMBLY SHELVES LIGHT FIXTURE MAINTENANCE FUNDAMENTALS REAR DOORS REAR DOORS MAINTENANCE FUNDAMENTALS BALLAST ACCESS...

Page 3: ...SERVICE section in this manual for sample serial labels COMPLIANCE Performance issues when in violation of applicable NEC federal state and local electrical and plumbing codes are not covered by warra...

Page 4: ...ther related location CAUTION CHECK EVAPORATOR PAN POSITIONS AND PLUG Water on flooring can cause extensive damage Before powering up unit check the following Hot gas evap pan MUST BE positioned direc...

Page 5: ...ramp and off from skid Note Illustrations reflect general outline of sample case and may not reflect your particular model or options Support case while sliding down ramp Ramp Various Types Of Case Sh...

Page 6: ...r of the unit Electrical leads connections are provided in the junction box 3 Optional Remote Refrigeration System Note Servicing units is to be done by refrigeration electrical contractors only Elect...

Page 7: ...Access Box Typ Secondary Case At Center Secondary Case At Right Note Daisy Chain Synchronous Wiring Must Route To Primary Case At Left Adjoined cases have synchronous defrosts Synchronous Defrost Plu...

Page 8: ...e is adjoined and bolted form 1 OUTER sanitation bead as shown into any cavities or gaps that may remain along outer adjoinment areas where butyl has ALREADY been applied Also place a thick bead of ca...

Page 9: ...the Left Case when facing cases When properly installed it will be flush with inside edge of left Case tab to allow for seamless adjoining of Cases Note Enlarged views at right show proper placement o...

Page 10: ...t at the factory supply air is set for a case temp at 5 C 41 F as as determined by the case size The temperature is controlled by a thermostat See illustration at right for thermostat location If a te...

Page 11: ...wered key may be turned clockwise to lock latch into strike bracket Turn counter clockwise to unlock Keep keys in safe and secure place Latch 11 OPTIONAL ROLL DOWN SECURITY DOOR SEE NEXT PAGE FOR EXTE...

Page 12: ...rike bracket Turn counter clockwise to unlock Keep keys in safe and secure place See STIFFENER FOR OPTIONAL ROLL DOWN SECURITY DOOR PURPOSE REMOVABILITY section on next page Latch 12 OPTIONAL ROLL DOW...

Page 13: ...ned to hold stiffener in place Brackets are at upper and lower sections of case Brackets are at center and left side of case Stiffener slots are to be held in place by bracket prongs at upper section...

Page 14: ...on of operating manual Replacement of lamp To replace LED Light Fixture simply disconnect the existing LED light from its brackets and or self adhesive tape Replace Note LED Light and Plug must be con...

Page 15: ...ollapse the honeycomb to allow it to be pulled out of honeycomb retainer C Pry downward and away from honeycomb retainer Clean honeycomb with warm water and soap solution Submerse if necessary Use bru...

Page 16: ...t of the angle of the shelf can be made not the position Adjustments to the shelves can be made by pivoting the lower portion of the shelf bracket in the upright The shelves can be adjusted to an angl...

Page 17: ...Optional Rear doors are hinged with handles to allow access to case from rear Handles and strike plates allow doors to securely latch Illustration shown reflects model CO47R Your rear door size may va...

Page 18: ...ical contractor Remove rear grille by lifting up and off Ballast are mounted inside the electrical box Illustrations shown reflect models CO37R and CO67R Your model may slightly vary Rear View of Mode...

Page 19: ...teps if any Remove deck pan for coil fans access Caution Turn off main power before accessing the evaporator coil deck pan area Rotating blades can cause severe injury Model CO47R Shown Above Your Mod...

Page 20: ...by lifting up and off no screw removal required Slide out 6 8 9 10 1 3 5 2 1 Condenser Coil Shroud Optional May House Clean Sweep Automatic Condenser Coil Cleaner 6 Filter Drier 2 Condenser Coil Tubi...

Page 21: ...t grille by lifting up and off no screw removal required Slide out 6 8 9 10 1 3 5 2 1 Condenser Coil Shroud Optional May House Clean Sweep Automatic Condenser Coil Cleaner 6 Electrical Coil Overflow C...

Page 22: ...lifting up and off no screw removal is required Slide out 4 6 10 7 1 3 2 1 Embraco Compressor Start Components 6 Filter Drier 2 Refrigeration Pump 7 Automatic Condenser Coil Cleaner Driver 3 Hot Gas C...

Page 23: ...well as regulatory standards to which the case conforms For additional technical information and service see the TECHNICAL SERVICE page in this manual for instructions on contacting Structural Concep...

Page 24: ...Tub Drain Caution Due to rotating fans turn off case Disconnect plug from wall outlet before beginning tub drain cleaning Vacuum tub under decks Clean with soap and water solution Wipe dry with clean...

Page 25: ...lle no screw removal required Slide roll out condensing unit assembly at case front Remove the four 4 screws holding the Clean Sweep rails intact Remove the Clean Sweep rail Wash rails brushes in hot...

Page 26: ...hout Rinse thoroughly with spray bottle filled with clean water and sponge Quarterly Under Case Cleaning Once refrigeration package is clear of unit vacuum under case to remove all dust and dirt that...

Page 27: ...to adjust Product must be pre chilled before placing in case Check that the case is not in the sun or near a heat or air conditioning vent See OVERVIEW CONDITION COMPLIANCE WARNINGS PRECAUTIONS WIRIN...

Page 28: ...ndenser pan is operating properly Check that overflow condenser pan is properly plugged in or connected Caution Disruption of power can cause water to overflow pan and seep onto flooring causing damag...

Page 29: ...eck that the MAIN power switch is on Check that fans are plugged in at the fan shroud Check for foreign material obstructing fan performance Check that fan blades freely rotate within fan shrouds Chec...

Page 30: ...that condenser coil has been cleaned Check air return grilles for obstructions Check sight glass for flashing and or low charge Check Set Point Temperature it may be adjusted too high Condensing Unit...

Page 31: ...timeout occur normal operational settings prior to modifications being made will resume 3 If the instrument is switched off before pressing the Prg key all modifications to parameters will be lost Set...

Page 32: ...set reset HACCP alarms reset temp monitoring Summary Table of Alarm and Signals Display Buzzer and Relay Integrated Electronic Microprocessor Controller Read And Save These Instructions Page 2 of 3 Us...

Page 33: ...tor min F 1 250 d6 Display on hold during defrost C 0 2 dd Dripping time after defrost min F 0 15 d 1 Display of defrost probe 1 C F F 5 Select Celsius C or Fahrenheit F flag C 0 1 33 For Case Specifi...

Page 34: ...ttorney fees and costs Remedies of SCC SCC s rights and remedies shall be cumulative and may be exercised from time to time In a proceeding or action relating to the breach of this Agreement by Purcha...

Reviews: