5.3.1
Electrical connections
All contact connectors can be found within the switch housing. The earth conductor for grounding the housing
can be found on the bearing plate. The electrical connections for contact connectors and earth conductors occur
via screw connections. The bores for cable entry points are closed with blind plugs for delivery of the switch.
The bores can be found in the gearbox housing. Depending on the cable type used, the corresponding blind
plugs are replaced through cable entry points by the customer. The cable ends reach the contacts via the cable
entry point on the connecting terminals. Each contact is provided with protection against accidental contact.
NOTE
For contact 51, the following applies:
The protection against accidental contact must be removed for wiring.
DANGER
Risk of accidents caused by live components
There are live components in the area of the electrical connections.
► After wiring, each contact must be provided with protection against accidental contact according to
the Low Voltage Directive 73/23 EWG.
► Connect the marked earth conductor to the bearing plate with the earth conductor.
• Cable entry points: see dimension sheet.
• Contact connector wiring:
• for every 2 solid-core or 2 multi-stranded copper wires with wire end sleeves,
• Wire cross-section: 0.75 mm
2
to 2,5 mm
2
, AWG 20 ... 14,
• Tightening torques, see section 6.2.3.
5.3.2
Mounting position
The mounting position of the GTES is optional.
21