10
DRAIN OFF COCK
ISOLATING VALVE
SAFETY
PUMP
PRESSURE GAUGE
TEMPERATURE GAUGE
AUTO AIR VENT
HEAT STORE
STREBEL
Fill
DHW
THERMAL VALVE COLD WATER
SUPPLY TO REGULATIONS
See your quotation for items
that are supplied. Positions &
orientation below are for ease
of illustration
HYDRAULIC SCHEME
AUTOMATIC 3 PORT MIXING
VALVE for maintained return
temperature
EXPANSION VESSEL
SEALED SYSTEM
The installer must fit a cold water supply (1/2“
connection) and comply fully with regulations in
force
A certified safety valve not exceeding 2.5 bar
must be installed in the heating system. The
safety valve sizing should be to current regula-
tions. Do not install other valves between the
safety valve and boiler. The water return temper-
ature must not fall below 60 °C to prevent the
build up of condensate inside the boiler.