![Stratus ftServer V 2302 Site Planning Manual Download Page 60](http://html1.mh-extra.com/html/stratus/ftserver-v-2302/ftserver-v-2302_site-planning-manual_1383770060.webp)
System Specifications
A-4
Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide
(R624)
Table A-2. V 2302, V 4304, and V 6308 System CPU-I
O Enclosure: Specifications
(Page 1 of 2)
Power
Input power
ftServer 2302 and 4304: 500W for each enclosure (1000W total)
ftServer 6308: 750W for each enclosure (1500W total)
Nominal input voltage
200-240VAC; 50/60 Hz
Protective earth ground current
3.5 mA maximum for each AC power cord
Physical Dimensions
Height
7.0 in. (17.78 cm; 4U)
Width
17.50 in. (44.45 cm)
Depth
30 in. (76.2 cm), excluding screws and bezel
Weight, including 6 DIMMS, 4
processors
Two enclosures: 101 lb. (45.8 kg), fully loaded
Rails and shelf unit: 13.8 lb (6.26 kg)
Environmental
Operating temperature
41
F to 95
F (5
C to 35
C)
For every 800 ft (243.8 m) above 2000 ft (609.6 m), lower the
maximum operating temperature by 1
C.
Storage temperature
-38
F to 140
F (-40
C to 60
C), vented
Operating altitude
0 ft to 10,000 ft (0m to 3,048m)
Maximum rate of temperature
change during operation
12
C per hour
Relative humidity during
operation
20% to 80% (noncondensing)
Relative humidity during storage
20% to 80%
Heat dissipation, each system
(both enclosures)
ftServer V 2302 and V 4304: 3412
ftServer V 6308: 5118 BTUs per hour
Air cleanliness
Meets ISO 14644-1 class 8 standards