AC Power Service Requirements
4-4
Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
Use the following worksheets to determine AC power requirements for the site.
•
In
, determine the power requirements at the A-side power source.
•
In
, determine the power requirements at the B-side power source.
•
In
, determine the power requirements for components outside of the
cabinet. These components can share a power source with the A-side or B-side
components.
The power service must be properly wired and grounded according to local standards
and regulations. See
for electrical circuit and wiring information.
To determine power receptacle requirements
1. In the Quantity column, write the number of each type of component.
2. Multiply the entry in the Quantity column by the number in the @ Power (Watts)
column, and enter the result in the AC Power (Extended) column.
3. Add the values in the AC Power (Extended) column, and enter the sum on the
bottom line. This value indicates the maximum power requirement for each power
source.
Table 4-5. Worksheet for Determining A-Side Power Requirements
System Component
Quantity
@ Power
(Watts)
AC Power
(Extended)
ftServer 6600 system
x
1300
=
ftServer 5600 system
x
650
=
ftServer 3300 system
x
500
=
x
300
=
x
21
=
x
20
=
T521 and T522 tape drive
enclosure
x
500
TOTAL A-SIDE POWER REQUIREMENTS
Summary of Contents for ftserver 3300
Page 1: ...Stratus Technologies R553 01 Stratus ftServer 3300 5600 and 6600 Site Planning Guide...
Page 14: ...Preface xiv Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...
Page 24: ...System Documentation 1 10 Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...
Page 32: ...Planning for Cables 3 4 Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...
Page 50: ...Stratus Supplied Power Cords 4 18 Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...
Page 133: ...Standards Compliance Standards Compliance D 3 VCCI Note BSMI Note...
Page 134: ...Standards Compliance D 4 Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...
Page 138: ...Index Index 4 Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...