AAP41104 PDU Specifications
Specifications of Peripheral and Storage Components
B-11
Table B-6. AAP41104 PDU Specifications
Power
Output wattage
N/A
Nominal input voltage;
Frequency range
200–240 volts AC; 50–60 Hz
Physical Dimensions
Height
1.75 in. (4.45 cm)
Width
19.1 in. (48.51 cm)
Depth
6.75 in. (17.15 cm)
Environmental
Operating temperature during
operation
41
°
F to 95
°
F (5
°
C to 35
°
C)
For every 800 ft (243.8m) above 2,000 ft (609.6m),
lower the maximum operating temperature (35
°
C) by
1
°
C.
Maximum rate of temperature
change during operation
12
°
C per hour or 0.2
°
C per minute
Relative humidity during
operation
10% to 80% (noncondensing)
Storage temperature to
40,000 ft (12.2 km)
-38
°
F to 140
°
F (-40
°
C to 60
°
C)
Relative humidity during
storage
5% to 95% (noncondensing)
Summary of Contents for ftserver 3300
Page 1: ...Stratus Technologies R553 01 Stratus ftServer 3300 5600 and 6600 Site Planning Guide...
Page 14: ...Preface xiv Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...
Page 24: ...System Documentation 1 10 Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...
Page 32: ...Planning for Cables 3 4 Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...
Page 50: ...Stratus Supplied Power Cords 4 18 Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...
Page 133: ...Standards Compliance Standards Compliance D 3 VCCI Note BSMI Note...
Page 134: ...Standards Compliance D 4 Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...
Page 138: ...Index Index 4 Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...