Grounding Requirements
Electrical Power Planning
2-17
Grounding Requirements
W A R N I N G
!
Incorrect grounding can cause severe personal injury
and extensive equipment damage.
The ftServer system obtains an earth reference ground over independent ground
connections to the cabinet frame. Ensure that a high-integrity safety-ground conductor
is installed as part of the wiring system.
See
“Grounding Considerations” on page B-1
for a more complete discussion of
ftServer system grounding.
B50175
IEC 60320 C19 to NEMA L6-20P,
PSE approved
20A/250V
15 ft
Japan locking
power cord
Table 2-15. AC Power Cords to Connect PDUs to a UPS
Marketing ID
Plug Type
Rating
Length
Locale
B50171F
IEC 60320 C19 to NEMA L6-20P
16A/250V
15 ft
North America
B52700F-45M
IEC 60320 C19 to IEC 60320 -C20
20A/250V
4.5m
International
B50175
IEC 60320 C19 to NEMA L6-20P,
PSE approved
20A/250V
15 ft
Japan locking
power cord
Table 2-16. System Power (Jumper) Cables to Connect ftServer Systems to PDUs
Marketing ID
Plug Type to System
Plug Type to PDU
Rating
Length
B50502F
IEC 60320 C13
IEC 60320 C14
10A/250V
2.0m
B50503F
IEC 60320 C13
IEC 60320 C14
10A/250V
2.0m
Table 2-14. Power Cords to Connect PDUs Directly to AC Power Mains (Continued)
Summary of Contents for ftServer 2510
Page 1: ...Stratus Technologies R627 04A Stratus ftServer 2510 4410 and 6210 Systems Site Planning Guide...
Page 8: ...Tables viii Stratus ftServer 2510 4410 and 6210 Systems Site Planning Guide R627...
Page 12: ...Preface xii Stratus ftServer 2510 4410 and 6210 Systems Site Planning Guide R627...
Page 50: ...Planning for Cables 3 4 Stratus ftServer 2510 4410 and 6210 Systems Site Planning Guide R627...
Page 104: ...Index Index 4 Stratus ftServer 2510 4410 and 6210 Systems Site Planning Guide R627...