background image

                                                               
    

 

7

Maintenance. 

 

Stokvis EP units have been designed to be easy to maintain, thus ensuring trouble-free operation. 
 
On two pump units the duty pump will automatically rotate per operation, to equalise wear and to 
exercise the standby pump. 
 
At regular intervals, but all least every six months, the following points should be checked. 

1)  

Bleed a little water from the system when at ambient temperature, and check that the pump 

 

cut-in and cut-out pressures are as shown in the table of settings attached.  

 

On two pump units continue to bleed water from the system, at a rate greater than approx. 

 

0.75gpm, once the duty pump has started.  

 

This will cause the standby pump to start.  

 

Once the standby pump has started, close the bleed and allow the pressure to rise, noting the 

 

pressure at which the pumps switch off.  

 

If necessary adjust the pressure switch (es) to achieve the correct pressure settings.  

 

Check that the pump(s) run, without excessive noise or vibration and do not leak from the 

 

mechanical seal, either when running or when stationary. 

2)  

Using the isolating valve provided within the unit to isolate the system from the pressure 

 

sensing line, bleed off a few drops of water from the sensing line, having first switched the 

 

pump (s) off.  

 

The pressure within the sensing line will drop, as indicated by the unit gauge.  

 

Check that the switch resets before cold fill pressure is reached. 

 

Close the valve between the unit and system and expansion vessels.  

 

Run the pump, raising the pressure and check that the system high pressure alarm switch 

 

operates at the correct pressure.  

 

Switch off the pump and open isolating valve.  

 

If necessary, adjust the pressure switch (es) to achieve the correct pressure settings. 

3)  

Check the pre-charge pressures in both the unit pressure vessel and system expansion 

 vessel(s). 

 

 

Isolate and drain all water from vessels before checking pre-charge pressure at the Schrader 

 

valve, with suitable pressure gauge.  

 

When a checking the pre-charge pressure, note if any water vapour is exhausted from the 

 

Schrader valve.  

 

If this is the case, then the vessel diaphragm has become perforated, and either the 

 

diaphragm (or complete vessel, if it is a fixed diaphragm type), must be replaced. 

4)  

Check over all electrical equipment, checking operation of relays, Mcb’s, lamps, etc. 

 

Check all terminals are tight. Generally clean within the enclosure. 

5)  

Check operation of unit ball valve, ensuring valve will open, and close drip-tight. Lubricate the 

 

fulcrum and/or strip and clean if necessary.  

 

Check inside break tank for any debris or sediment and if necessary drain tank and clean out.  

 

If larger amounts of sediment are found regularly, check the system for leakage. 

6)  

Generally check over and clean the exterior of the unit, at the same time checking for leaks. 

 

 

 

Summary of Contents for ECONOPRESS EP 1

Page 1: ...G UNITS INCLUDING H P UNITS OPERATING AND MAINTENANCE INSTRUCTIONS STOKVIS ENERGY SYSTEMS 96R WALTON ROAD EAST MOLESEY SURREY KT8 0DL TEL 08707 707 747 FAX 08707 707 767 E MAIL info stokvisboilers com...

Page 2: ...2 Contents Contents 2 General Description 3 Storage 4 Installation 4 Unit 5 Commissioning 5 Maintenance 7 Spare and service 8 General data Error Bookmark not defined...

Page 3: ...ressure the standby pump EP 2 units will start as the pressure falls further If the pressure within the system goes beyond preset design limits then the system pressure alarm switches will become acti...

Page 4: ...ther on a smooth level surface or alternatively back fixed to a suitable wall or other vertical structure in areas which are dry well ventilated and free from any danger from frost Once the unit has b...

Page 5: ...ctions Any parts removed for transit must be refitted The above in conjunction with the drawings should enable the unit to be installed ready for commissioning however if you require advice or assista...

Page 6: ...al switch on at low pressure the standby pump will run to cut out pressure and stop whereupon the duty pump will start and run to its cut out pressure On falling pressure the duty pump will start at i...

Page 7: ...p as indicated by the unit gauge Check that the switch resets before cold fill pressure is reached Close the valve between the unit and system and expansion vessels Run the pump raising the pressure a...

Page 8: ...records of all units supplied General data EP1 EP1HP EP2 EP2HP FACTORY SETTINGS Duty pump cut in pressure 2 5 BAR 6 BAR 2 5 BAR 6 BAR Standby pump cut in pressure N A N A 2 3 BAR 5 8 BAR SE vessel pre...

Page 9: ......

Page 10: ......

Page 11: ......

Page 12: ......

Reviews: