Air / Flue pipe data
Concentric pipe nominal diam.
Ø
100/150
Tolerance female Ø internal
101 mm
150 mm
Single pipe nominal diam.
Ø100
Tolerance female Ø internal
101
±0.7
mm
Ø130
Tolerance female Ø internal
131
±0.7
mm
Material
PP (Concentric flue pipe) - Galva 0,4/Alluminium 1,3mm (Concentric air intake
pipe)
PP (single pipe)
Material seal
EPDM black for corrosion class 1 / Viton for corrosion class 2
Heat resistance
0 W/m
2
K
Wall thickness
2.2 mm
Temperature class:
T120
Pressure class:
P1 max. 200Pa / H1 max. 5000Pa
Corrosion class:
W1
Location class
Concentric pipe: Only outside buildings / Single pipe: Only inside buildings
Fire rating class
E
Outer wall class
(Concentric pipe only) L0
Distance to combustible materials
Concentric pipe: 00 mm / Single pipe: 30 mm
+1.0
- 0.5
+1.0
- 0.5
Installation
Air/Flue gas system
Flue Gas data
Boiler
type
Nominal heat
output
Nominal heat
input
Flue
gas
connection
(DN)
CO
ഺ
Level
Flue gas
temperature
Flue gas
quantity
Max
permissible
ÀXH
resistance
kW
kW
mm
%
°C
g/s
Pa
R40
max
min
max
min
max
min
max
min
max
min
max
min
45/50
45.7
7.7
46.9
100
76
33
26
4
150
15
65
10.1
62.4
10.4
100
35
6
150
15
13.4
100
47
7
150
15
100
92.9
15.6
95.2
16.0
100
52
9
150
15
120
111.6
114.3
19.2
100
62
11
200
15
150
132.2
23.3
135.5
23.9
130
74
12
200
15