Neutralisation
General
Neutralisation systems
15
General
Condensate, created by the
R40, should be drained into the public
draining system. The condensate PH is
between 3.0 and 3.5. National and/or
local regulations have to be checked, in
order to find out whether the
condensa
te should be neutralised before
entering
the public draining system.
Type
DN2
DN3
Applicable for
[kW]
450
1500
Length
[mm]
420
640
Width
[mm]
300
400
Height
[mm]
240
240
DN1
75
320
200
230
Type
HN1.5 HN2.5
Applicable for
[kW]
280
540
Length
[mm]
410
640
Width
[mm]
300
400
Height
[mm]
290
240
Power con-
sumption pump
[W]
40
150
Pump head
[m]
6
3
HN2.7
750
640
400
320
45
4
Neutralisation systems
The neutralisation systems can be
pla
ced in the bottom section of the boiler.
The delivery of the system contains the
following components:
Granulate for first filling
Connection hoses for inlet and outlet
connection
Boiler connection adapter
For the neutralisation two different
sys
tems are available:
Standard neutralisation system (DN)
The standard neutrlisation system is used, when the public draining connection is
at lower level than the boiler syphon connection.
Neutralisation system with pump (HN)
The neutralisation system with pump is used, when the public draining system is at higher level than the boiler syphon
con
nection and the condensate needs to be transported to a higher level before draining is possible. The built-in pump
of the
neutralisation system takes care of the transport of the condensate.
The maximum amount of condensate
for each boiler type can be found in the
chapter
"
Technical data
"
.