background image

INSTallaTION 

 

Preparation

8

 | WPE-I HW 230 GB Premium 

www.stiebel-eltron.com

8.2  Installation site

!

 

Material losses

 

f

Install the appliance only in rooms without a con-

stant ignition source (e.g. open flames, a live gas 

appliance or an electric heater) or without open flue 

boilers.

 

Note

The appliance is designed for indoor installation, except 

in damp areas.

 

f

Never install the appliance directly below or next to bed-

rooms.

 

f

Implement pipe outlets through walls and ceilings with an-

ti-vibration insulation.

The room in which the appliance is to be installed must meet the 

following conditions:

 

- No risk from frost

 

- The room must not be subject to a risk of explosions arising 

from dust, gases or vapours.

 

- When installing the appliance in a boiler room together with 

other heating equipment, ensure that the operation of other 

heating equipment will not be impaired.

 

- The minimum volume of the installation room must be ob-

served (see chapter "Preparation / Safety concept").

 

- Load bearing floor (for the weight of the appliance, see chap-

ter "Specification / Data table").

 

f

Ensure that the safety valve for the brine circuit is installed 

in the installation room. Alternatively, outdoor installation is 

also possible.

 

f

Ensure that the substrate is level, even, solid and permanent.

 

f

For installation on floating screeds, make provisions for quiet 

heat pump operation.

 

f

Isolate the installation surface around the heat pump by 

means of a recess. After completing the installation, seal the 

recess with a waterproof, sound insulating material, such as 

silicone.

1 2 3

5

4

26

0

3

01

1

46

6

1  Concrete base

2  Impact sound insulation

3  Floating screed

4  Floor covering

5  Recess

8.3  Minimum clearances

≥500

≥200

≥1000

≥50

≥500

D

00000

33

99

2

 

f

Maintain the minimum clearances to ensure trouble-free op-

eration of the appliance and facilitate maintenance work.

Summary of Contents for WPE-I 04 HW 230 GB Premium

Page 1: ...OPERATION AND INSTALLATION Ground source heat pump WPE I 04 HW 230 GB Premium WPE I 06 HW 230 GB Premium WPE I 08 HW 230 GB Premium WPE I 12 HW 230 GB Premium WPE I 15 HW 230 GB Premium ...

Page 2: ...g the heat source system 12 9 5 Heating water connection 13 9 6 Oxygen diffusion 14 9 7 Filling the heating system 14 9 8 Venting the heating system 15 9 9 DHW connection 15 9 10 DHW circulation connection 16 9 11 Operation with buffer cylinder 16 9 12 Fitting the push fit connectors 16 10 Electrical connection 18 10 1 General 18 10 2 Electrical connection 18 10 3 High limit safety cut out for are...

Page 3: ...C Maintenance work such as checking the elec trical safety must only be carried out by a qualified contractor We recommend regular inspection to es tablish the current condition of the system and maintenance by a qualified contractor if required to return the system to its original condition Following disconnection from the power sup ply parts of the appliance may remain ener gised for 5 minutes u...

Page 4: ... in serious injury or death CAUTION Failure to observe this information may result in non seri ous or minor injury 1 3 Other symbols in this documentation Note General information is identified by the adjacent symbol f Read these texts carefully Symbol Meaning Material losses appliance damage consequential losses and environmen tal pollution Appliance disposal f This symbol indicates that you have...

Page 5: ... 3 Test symbols See type plate on the appliance 3 Appliance description The appliance is a ground source heat pump suitable for operation as a heating heat pump The heat pump extracts energy from the heat source medium at a low temperature level This extracted energy is then transferred to the heating water at a higher level augmented by the electric energy drawn by the compressor The heating wate...

Page 6: ...bserve all applicable national and regional regulations and instructions 7 Appliance description 7 1 Function The heat exchanger on the heat source side evaporator extracts natural heat from the heat source This extracted energy and the energy drawn by the compressor drive is transferred to the heating water by a heat exchanger on the heating water side condenser Subject to the heat load the heati...

Page 7: ... Increasing the minimum installation area If the minimum installation area requirement cannot be met in the installation room the installation room can be connected to a neighbouring room via ventilation apertures The ventilation apertures must be located near the ceiling and the floor If the ceiling is suspended and there is no wall to the next room the upper ventilation aperture can be dispensed...

Page 8: ...ion of other heating equipment will not be impaired The minimum volume of the installation room must be ob served see chapter Preparation Safety concept Load bearing floor for the weight of the appliance see chap ter Specification Data table f Ensure that the safety valve for the brine circuit is installed in the installation room Alternatively outdoor installation is also possible f Ensure that t...

Page 9: ...12 HW 230 GB Premium WPE I 15 HW 230 GB Premium Fuse protec tion Assignment Cable cross section B 25 A Compressor 4 0 mm when routing in a wall 2 5 mm when routing above the surface Alternatively 1x B 16 A Compressor 4 0 mm when routing in a wall 2 5 mm when routing above the surface B 16 A Electric emergency booster heater BH 2 5 mm 1 5 mm with only two live cores and routing on a wall or in an e...

Page 10: ...0088165 1 2 2 1 Hinge closer 2 Articulated joint f Unscrew the hinge closer f Unscrew both articulated joints f Undo the cable ties and pull the BUS cable connector from the programming unit f Place the connector safely in the refrigeration unit 3 1 1 2 0 2 D0000037450 f Pull off the front panel to the left Removing the upper side panels 1 1 2 2 D0000037451 f Remove the screws f Remove the side pa...

Page 11: ...r f Mark the immersion pipe f Place the DHW temperature sensor safely in the refrigerant circuit 4x D0000037500 f Undo the hydraulic connection lines D0000094165 f Fit the handles 4x D0000037499 1 2 1 Fixing screw 2 Handle f Remove the four fixing screws f Lift the refrigeration unit off the DHW cylinder f Position the DHW cylinder on the prepared base see chapter Installation Siting f Reassemble ...

Page 12: ... heat exchang er f Fill the intermediate circuit with an ethylene glycol water mixture with at least 25 by vol ethylene glycol Check for leaks f In the heat pump manager set the source medium to WATER The minimum return source tempera ture is set automatically to 2 C Permitted brine Part number MEG 10 Heat transfer medium as concentrate on an ethylene glycol base 231109 MEG 30 Heat transfer medium...

Page 13: ...e the sealing panel f Fill the brine circuit via the drain f Vent the brine circuit Check the brine concentration f Determine the density of the glycol water mixture e g with a hydrometer Using the actual density and temperature you can check the actual concentration in the diagram Note The quoted output data relates to ethylene glycol see Specification 1 10 1 09 1 08 1 07 1 06 1 04 1 03 1 02 1 01...

Page 14: ...parate the heating system between the heating circuit and the buff er cylinder Material losses The products of corrosion e g rusty sludge can set tle in the heating system components which may re sult in a lower output or fault shutdowns due to reduced cross sections 9 7 Filling the heating system Heating water quality Carry out a fill water analysis before filling the system This analy sis may fo...

Page 15: ...rovided in the pack is fitted to the cold water supply with the exception of the T P valve which is fitted at the top of the DHW cylinder DHW cylinder relief valve connections should not be used for other purpose No valve should be fitted between the expansion valve and the DHW cylinder f To obtain a balanced water pressure in the cold water and DHW lines position the cold water outlet directly on...

Page 16: ...1 Cap f Detach the panel f Remove the foam parts f Unscrew the cap f Reinsert the foam parts f Connect the DHW circulation line 9 11 Operation with buffer cylinder f Install the supplied TAF PT immersion contact sensor f Connect the sensor to the heat pump manager f Adjust the parameter Parameter Setting BUFFER OPERATION SETTINGS HEATING STANDARD SETTINGS ON 9 12 Fitting the push fit connectors D0...

Page 17: ...rs later need to be undone proceed as follows f Turn the screw cap anti clockwise until there is a narrow gap of approx 2 mm Press the retainer back with your fingers and hold on to it f Pull out the inserted pipe D0000088521 9 12 2 Installing copper push fit connectors DHW side Note The copper push fit connectors are only designed for use in the DHW line Material losses To ensure the push fit con...

Page 18: ...located at the appliance control panel behind the upper panel For all connections use appropriate cables in accordance with local regulations f Route all cables and sensor leads through the entries provid ed in the back panel see chapter Specification Dimensions and connections You must be able to open the control panel during maintenance and repair work see chapter Installation Venting the heatin...

Page 19: ...al the heat pump will not start f If no ripple control receiver is fitted install a jumper be tween EVU1 and EVU2 10 2 2 Heat pump manager terminal assignment D0000071841 Safety extra low voltage X1 1 CAN A L H L H CAN connection for heat pump and WPE heat pump extension X1 2 CAN B L H L H CAN FES X1 3 Signal Earth 1 2 Outside sensor X1 4 Signal Earth 1 2 Buffer sensor heating circuit sensor 1 X1 ...

Page 20: ...c tions for the heat pump manager see chapter Connecting external components 11 Commissioning Only a qualified contractor may adjust the settings in the commis sioning instructions for the heat pump manager commission the appliance and instruct the operator in its use Carry out commissioning in accordance with these operating and installation instructions and the instructions for the heat pump man...

Page 21: ...a remote control f At different outside temperatures e g 10 C and 10 C adjust the heating curve so that the required temperature is set in the lead room Standard values to begin with Parameter Underfloor heating Radiator heating system Heating curve 0 4 0 8 Control dynamic 100 100 Comfort temperature 20 C 20 C f If the room temperature in spring and autumn is too low approx 10 C outside temperatur...

Page 22: ...iance isolate it from the power supply at the terminal area Following disconnection from the power supply parts of the appliance may remain energised for 5 minutes until the inverter capacitors have discharged Note f Please observe the instructions for the heat pump manager Note The following inspection instructions may only be carried out by a qualified contractor Note When you open the appliance...

Page 23: ...97 1 2 3 4 1 Reset button 2 DIP switch WP Typ 3 DIP switch BA 4 LEDs DIP switch WP Typ The DIP switch WP Typ on the IWS serves to set the relevant heat pump type Factory setting Compressor mode with electric emergency booster heater WP Typ ON 1 2 3 4 D0000057054 f Check whether the DIP switch is set correctly Compressor mode with an external second heat generator Material losses In this case do no...

Page 24: ...uired for generating the necessary negative pressure f Replace the sealing tape if required We recommend a regular inspection to establish the current con dition of the system and maintenance if required to return the system to its original condition f Check the discharge aperture on the top of the appliance and the intake aperture on the side of the appliance visual check Remove any contaminants ...

Page 25: ...mium 25 1 2 26_03_01_1345 1 white protective anode OK 2 red replace protective anodes 1 2 26_03_01_1758 1 Protective anode without consumption indicator 2 Protective anode with consumption indicator Material losses Install the protective anodes as shown in the diagram ...

Page 26: ...cification 26 WPE I HW 230 GB Premium www stiebel eltron com 16 Specification 16 1 Dimensions and connections 1940 1600 600 401 1154 104 174 289 359 429 499 719 20 40 f02 e01 c06 c12 c10 f01 e02 c01 c13 984 D0000095572 ...

Page 27: ...valve 13 Cylinder 14 DHW outlet 15 T P valve 16 Metal discharge pipe D1 from T P valve to tundish 17 Expansion vessel 18 Expansion valve Note If a secondary return circuits are used then an additional expansion vessel may be required Note The tundish should be installed away from electrical de vices Data table Minimum size of discharge pipe D1 mm 15 Minimum size of discharge pipe D2 from tundish m...

Page 28: ...4 1 2 3 4 1 2 3 4 5 6 7 X12 9 X12 8 1 2 3 4 5 X12 10 X12 11 X11 2 1 2 X11 3 1 2 N Kühlen X11 4 1 2 N Ölsumpfheizung X11 5 1 2 3 X11 6 1 2 3 X11 7 1 2 3 X11 8 1 2 3 X11 9 1 2 3 X11 10 1 2 3 Netzversorgung Inverter 2 1 2 1 2 1 2 1 5 4 3 2 1 5 4 3 2 1 4 3 2 1 4 3 2 1 6 5 4 3 2 1 2 1 3 2 1 3 2 1 4 3 2 1 X72 KF20 KF21 KF22 X71 X70 X69 X68 X67 X66 X65 X64 X63 X62 X61 X60 AA07 MFG L H PWM GND M 1 MA10 ws...

Page 29: ... 8 X2 7 X2 6 X2 5 X2 4 X2 3 X2 2 X2 1 Heizkreispumpe 1 Heizkreispumpe 2 Mischer Heizkreis 2 Solarpumpe Störausgang Pufferfühler Heizkreisfühler 1 2 Wärmeerzeuger Fühler PWM Ausgang 1 Heizkreisfühler 2 VL Kühlen Zirkulationsfühler Analogeingang 0 10V Analogeingang 0 10V AA06 AA01 WPM4 H L N L BT20 Außentemperaturfühler Vorlauffühler Heizkreisfühler 3 Fernbedienung FE7 Telefonfernschalter Heizkurven...

Page 30: ...er valve motor MA10 Circulation pump MA12 Motor diverter valve for DHW heating MA25 Heat source pump motor MA26 Suction fan RF01 Snap on ferrite bead compressor cable emergency booster heater cable RF02 Snap on ferrite bead emergency booster heater cable RF03 Snap on ferrite bead WPM cable XD1 Terminal external emergency booster heater HP power supply XD3 External control terminal XD20 Distributio...

Page 31: ...Installation Specification www stiebel eltron com WPE I HW 230 GB Premium 31 ...

Page 32: ...1 2 3 4 5 1 2 3 4 7 8 9 10 D0000097156 X Inlet temperature of the WQA medium C Y Heating output kW Flow temperature 35 C 55 C Output Hz 1 Min 2 40 3 60 4 80 7 Min 8 40 9 60 10 80 Power consumption 0 1 2 5 4 3 2 1 0 1 2 3 4 5 1 2 3 4 5 6 D0000093976 X Inlet temperature of the WQA medium C Y Power consumption kW Flow temperature 35 C 55 C Output 1 1 2 50 3 100 4 1 5 50 6 100 ...

Page 33: ...m WPE I HW 230 GB Premium 33 Coefficient of performance 0 1 2 3 4 5 6 5 4 3 2 1 0 1 2 3 4 5 1 2 3 4 5 6 D0000093976 X Inlet temperature of the WQA medium C Y Coefficient of performance e Flow temperature 35 C 55 C Output 1 1 2 50 3 100 4 1 5 50 6 100 ...

Page 34: ...5 7 8 9 10 11 D0000097156 X Inlet temperature of the WQA medium C Y Heating output kW Flow temperature 35 C 55 C Output Hz 1 Min 2 40 3 60 4 80 5 100 7 Min 8 40 9 60 10 80 11 100 Power consumption 0 1 2 3 5 4 3 2 1 0 1 2 3 4 5 1 2 3 4 5 6 D0000093976 X Inlet temperature of the WQA medium C Y Power consumption kW Flow temperature 35 C 55 C Output 1 1 2 50 3 100 4 1 5 50 6 100 ...

Page 35: ...m WPE I HW 230 GB Premium 35 Coefficient of performance 0 1 2 3 4 5 6 5 4 3 2 1 0 1 2 3 4 5 1 2 3 4 5 6 D0000093976 X Inlet temperature of the WQA medium C Y Coefficient of performance e Flow temperature 35 C 55 C Output 1 1 2 50 3 100 4 1 5 50 6 100 ...

Page 36: ...10 11 12 D0000097156 X Inlet temperature of the WQA medium C Y Heating output kW Flow temperature 35 C 55 C Output Hz 1 Min 2 40 3 60 4 80 5 100 6 Max 7 Min 8 40 9 60 10 80 11 100 12 Max Power consumption 0 1 1 2 2 3 3 5 4 3 2 1 0 1 2 3 4 5 1 2 3 4 5 6 D0000093976 X Inlet temperature of the WQA medium C Y Power consumption kW Flow temperature 35 C 55 C Output 1 1 2 50 3 100 4 1 5 50 6 100 ...

Page 37: ...m WPE I HW 230 GB Premium 37 Coefficient of performance 0 1 2 3 4 5 6 5 4 3 2 1 0 1 2 3 4 5 1 2 3 4 5 6 D0000093976 X Inlet temperature of the WQA medium C Y Coefficient of performance e Flow temperature 35 C 55 C Output 1 1 2 50 3 100 4 1 5 50 6 100 ...

Page 38: ... 7 8 9 10 11 D0000097156 X Inlet temperature of the WQA medium C Y Heating output kW Flow temperature 35 C 55 C Output Hz 1 Min 2 40 3 60 4 80 5 100 7 Min 8 40 9 60 10 80 11 100 Power consumption 0 1 2 3 4 5 5 4 3 2 1 0 1 2 3 4 5 1 2 3 4 5 6 D0000093976 X Inlet temperature of the WQA medium C Y Power consumption kW Flow temperature 35 C 55 C Output 1 1 2 50 3 100 4 1 5 50 6 100 ...

Page 39: ...m WPE I HW 230 GB Premium 39 Coefficient of performance 0 1 2 3 4 5 6 5 4 3 2 1 0 1 2 3 4 5 1 2 3 4 5 6 D0000093976 X Inlet temperature of the WQA medium C Y Coefficient of performance e Flow temperature 35 C 55 C Output 1 1 2 50 3 100 4 1 5 50 6 100 ...

Page 40: ... 10 11 12 D0000097156 X Inlet temperature of the WQA medium C Y Heating output kW Flow temperature 35 C 55 C Output Hz 1 Min 2 40 3 60 4 80 5 100 6 Max 7 Min 8 40 9 60 10 80 11 100 12 Max Power consumption 0 1 2 3 4 5 6 5 4 3 2 1 0 1 2 3 4 5 1 2 3 4 5 6 D0000093976 X Inlet temperature of the WQA medium C Y Power consumption kW Flow temperature 35 C 55 C Output 1 1 2 50 3 100 4 1 5 50 6 100 ...

Page 41: ...m WPE I HW 230 GB Premium 41 Coefficient of performance 0 1 2 3 4 5 6 5 4 3 2 1 0 1 2 3 4 5 1 2 3 4 5 6 D0000093976 X Inlet temperature of the WQA medium C Y Coefficient of performance e Flow temperature 35 C 55 C Output 1 1 2 50 3 100 4 1 5 50 6 100 ...

Page 42: ... pressure switch positive pressure MPa 0 07 0 07 0 07 0 07 0 07 Hydraulic data Cylinder capacity V l 175 175 175 162 162 Surface area heat exchanger m 2 1 2 1 2 1 3 5 3 5 Energy data Energy efficiency class moderate climate W55 W35 A A A A A A A A A A Energy efficiency class DHW heating with load profile XL A A A A A Standby energy consumption 24 h at 65 C kWh 1 9 1 9 1 9 1 9 1 9 Electrical data S...

Page 43: ...2 weeks after filling desalination mg l 0 1 0 1 0 1 0 1 0 1 Oxygen 8 12 weeks after filling softening mg l 0 02 0 02 0 02 0 02 0 02 Heat transfer medium requirements on the heat source side Ethylene glycol concentration geothermal collector Vol 33 33 33 33 33 Ethylene glycol concentration geothermal probe Vol 25 25 25 25 25 Values Min flow rate heating m h 0 3 0 3 0 3 0 3 0 3 Heating flow rate EN ...

Page 44: ...ued by those subsidiaries Such guarantee is only grant ed if the subsidiary has issued its own terms of guarantee No other guarantee will be granted We shall not provide any guarantee for appliances acquired in countries where we have no subsidiary to sell our products This will not affect warranties issued by any importers Environment and recycling We would ask you to help protect the environment...

Page 45: ...www stiebel eltron com WPE I HW 230 GB Premium 45 NOTES ...

Page 46: ...46 WPE I HW 230 GB Premium www stiebel eltron com NOTES ...

Page 47: ...www stiebel eltron com WPE I HW 230 GB Premium 47 NOTES ...

Page 48: ...ron cz www stiebel eltron cz Finland STIEBEL ELTRON OY Kapinakuja 1 04600 Mäntsälä Tel 020 720 9988 info stiebel eltron fi www stiebel eltron fi France STIEBEL ELTRON SAS 7 9 rue des Selliers B P 85107 57073 Metz Cédex 3 Tel 0387 7438 88 Fax 0387 7468 26 info stiebel eltron fr www stiebel eltron fr Hungary STIEBEL ELTRON Kft Gyár u 2 2040 Budaörs Tel 01 250 6055 Fax 01 368 8097 info stiebel eltron...

Reviews: