installation
Commissioning
13.4 Wpm3i commissioning report
The following lists the parameters that can be adjusted via the programming unit.
Programs / heat-up program
setting range
standard
system value
LOW END TEMPERATURE
20..40 °C
25.0 °C
TEMP. RISE PERIOD
0 to 5 days
2 days
MAXIMUM TEMPERATURE
20...50 °C, inc 0.5 K
40.0 °C
MAX TEMPERATURE DURATION
0 to 10 days
0 days
RISE PER DAY
1 to 10 K/day
1 K/day
settings / general
setting range
standard
system value
CONTRAST
01 to 10
5
BRIGHTNESS
0 to 100 %
50 %
TOUCH SENSITIVITY
01 to 10
04
TOUCH ACCELERATION
02 to 10
06
settings / heating / heating circuit 1
setting range
standard
system value
SET ROOM TEMP COMFORT
5 to 30 °C
20 °C
SET ROOM TEMP ECO
5 to 30 °C
20 °C
HEATING CURVE RISE
0.2 to 3
0.6
settings / heating / heating circuit 2
setting range
standard
system value
SET ROOM TEMP COMFORT
5 to 30 °C
20 °C
SET ROOM TEMP ECO
5 to 30 °C
20 °C
HEATING CURVE RISE
0.2 to 3
0.2
settings / heating / standard setting
setting range
standard
system value
BUFFER OPERAT
ON / OFF
OFF
SUMMER MODE
ON / OFF
ON
OUTSIDE TEMPERATURE
3 to 30 °C
20 °C
BUILDING HEAT BUFFER
1 to 3
1
MAXIMUM RETURN TEMP
20 to 55 °C
55 °C
MAXIMUM FLOW TEMP
20 to 65 °C
60 °C
MIXER DYNAMICS
30 to 240
100
MAXIMUM MIXER TEMPERATURE
20 to 90 °C
50 °C
FIXED VALUE OPERATION
OFF / 20 ..50 °C
OFF
OPTIMUM HEATING CURVE
OFF / 0.01 ..0.1
OFF
FROST PROTECT
-10 to 10 °C
4 °C
settings / heating / Fe7 remote control
setting range
standard
system value
HEATING CIRC PRESELECTION
1 / 2 heating circuits
Heating circuit 1
ROOM INFLUENCE
OFF / 0 to 20
5
ROOM CORRECTION
-5 to 5 K
0
settings / heating / pump cycles
setting range
standard
system value
PUMPCYCLES
ON / OFF
OFF
settings / heating / electric reheating
setting range
standard
system value
DUAL MODE TEMP HEATING
-40 to 40 °C
-20 °C
LOWER APP LIMIT HEATING
OFF / -39.5 to 40 °C
-20 °C
settings / DHW / DHW temperatures
setting range
standard
system value
SET DHW TEMP COMFORT
10 to 60 °C
50 °C
SET DHW TEMP ECO
10 to 60 °C
50 °C
settings / DHW / standard setting
setting range
standard
system value
DHW HYSTERESIS
1 to 10 K
5 K
DHW LEARNING FUNCTION
ON / OFF
OFF
DHW CORRECTION
0 to 5 °C
3 °C
COMBI CYLINDER
ON / OFF
OFF
PASTEURISATION
ON / OFF
OFF
settings / DHW / electric reheating
setting range
standard
system value
DUAL MODE TEMP DHW
-40 to 40 °C
-20 °C
LOWER APP LIMIT DHW
OFF / -39.5 to 40 °C
-20 °C