12
| LWZ 170 E PLUS / LWZ 370 PLUS WWW.STIEBEL-ELTRON.COM
INSTALLATION
Installation
10.2 Connecting the condensate drain
!
Material losses
Never kink the hose, to ensure the condensate drains per-
fectly. The fall must be at least 10 %, and the appliance
must be horizontal.
> 60
D
00000
46
57
2
2
1
1 Condensate drain
2 Condensate drain connector (Ø 32 mm) with union nut
The condensate drain is routed through the floor plate. The con-
densate must drain away via the domestic sewer system.
f
f
Secure the condensate drain connector supplied along with
the gasket and union nut to the condensate drain located un-
derneath the appliance.
You can fit the condensate drain pipe (bent if required) to this
condensate drain connector with a glued joint.
f
f
Before connecting the condensate drain to the appliance,
pour water into the siphon to create a stench trap.
The condensate drain pipe must terminate below the water level
in the siphon. The condensate drain pipe must be immersed in
the water in the siphon by at least 60 mm.
10.3 Connecting air ducts
During installation, ensure that no metal swarf enters the
ductwork. However, should this occur, remove this debris, other-
wise the fans may be damaged.
External wall ducts
Supply outdoor air from a location where contamination (dust,
soot, odours, flue gas, exhaust air) is as low as possible.
When installing external wall ducts, prevent any short circuit be-
tween the air intake and the air discharge.
Silencers
Always install a silencer in both the supply air duct and the extract
air duct. We recommend installing additional silencers if required
to avoid sound transmission.
If a room with a high noise level must be ventilated, install addi-
tional silencers upstream of this room to reduce sound transmis-
sion to adjacent rooms.
Aspects such as carried voices and impact sound must also be
taken into consideration in the case of ducts embedded in con-
crete. Carried voices should be avoided by designing the duct with
separate branches to the valves. If required, insulate the supply air
ducts, e.g. if they are outside the insulated wall panel.
Overflow apertures
In living rooms and bedrooms, air is only blown in. Air is only
extracted from rooms where odours and moisture are generated.
Ventilation grilles must be installed in internal doors or walls,
or the air gap beneath the door must be increased to ≥ 8 mm to
ensure an unobstructed air flow.
Insulation against condensation
!
Material losses
When warm air meets cold surfaces, condensation can
result.
f
f
For outdoor air and exhaust air ducts, use va-
pour-proof thermally insulated pipes.
f
f
If you use uninsulated pipes and moulded parts for
this pipework, ensure that they are adequately insu-
lated.
f
f
Insulate the supply air and extract air ducts if they
are routed through unheated rooms.
The extract air duct does not require a control valve, because the
necessary air flow rates are controlled by the appliance itself.